L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS

Table 6. L7224/L7248 Controller Operating Sequence.

 

 

Action

System Response

Thermostat calls for heat.

Circulator starts when water temperature is above Low Limit setting (if

 

applicable) or above the Thermal Purge Temperature Limit (tPL) if

 

Thermal Purge is enabled. Boiler temperature is checked. Burner

 

starts when water temperature is below High Limit setting minus the

 

differential or at or below the Thermal Purge Temperature Limit (tPL)

 

for cold start boilers if the Thermal Purge Temperature Limit is

 

enabled. If tPL is enabled, the burner may also start if the boiler

 

temperature is cooling at 10 ºF or greater per minute or the Thermal

 

Purge Time Delay (tPt) has expired.

 

If Anti Short-Cycle Time is enabled, the burner does not start until the

 

set Anti Short-Cycle Time between cycles expires after the previous

 

call for heat was satisfied.

 

 

Boiler temperature exceeds the High Limit.

Burner is turned off. Burner restarts when the water temperature

 

drops below the High Limit setting minus the Differential. If Thermal

 

Purge is enabled, the burner is turned on when either the Thermal

 

Purge Temperature Limit is reached, the Thermal Purge Time Delay

 

has expired or the boiler temperature cooling rate exceeds 10 ºF/

 

minute.

 

 

Thermostat is satisfied.

Circulator and burner turn off.

 

 

Boiler temperature drops below the Low Limit

Burner is turned on, Circulator is turned off. Burner stops when the

setting minus the differential (if applicable).

water temperature exceeds the Low Limit setting. Power to Zc is

 

removed.

 

 

Error condition

If an error condition is detected, all outputs except ZC are shut down.

1-5.

Burner is off. Control continues to function and restarts when error is

 

corrected.

 

During the error check sequence, the system checks for drift in the

 

sensor and corrosion in the connections.

 

 

Error condition 6.

EnviraCOM communication is not available.

 

 

Error condition 7.

The control has reset the High Limit, Low Limit and Differential setting to

 

a default setting and will continue to run at those settings.

 

Performance of the system will be degraded.

 

 

Error condition 8.

If the error condition is detected, all outputs except ZC are shut down.

 

Burner is off. Control continues to function and restarts when all three

 

user keys have been pressed longer than 60 seconds.

 

 

Error condition 9*.

System continues to run with no outdoor reset functionality

 

 

Error condition 10*.

System continues to run with outdoor reset parameters enabled as

 

programmed. Error cleared automatically.

 

 

Error condition 11*.

System continues to run with boiler temp set to High Limit.

 

 

* Error condition only available when the Outdoor Reset Module is installed.

Table 7. L7224/L7248 Controller Operating Sequence with multiple zones connected through the ZR terminal.

Action

System Response

Zone Request (ZR) terminal is connected to

Boiler temperature is checked. Burner starts when water temperature

L1 (Zone calls for heat).

is below High Limit setting or at or below the Thermal Purge

 

Temperature Limit (tPL) for cold start boilers if the Thermal Purge

 

Temperature Limit is enabled. If tPL is enabled, the burner may also

 

start if the boiler temperature is cooling at 10 ºF or greater per minute

 

or the Thermal Purge Time Delay (tPt) has expired. Anti Short-Cycle

 

Time is applied, see Table 6.

 

 

Boiler temperature exceeds the High Limit.

Burner is turned off. Burner restarts when the water temperature

 

drops below the High Limit setting minus the Differential. If Thermal

 

Purge is enabled, the burner is turned on when either the Thermal

 

Purge Temperature Limit is reached, the Thermal Purge Time Delay

 

has expired or the boiler temperature cooling rate exceeds 10 ºF/

 

minute.

 

 

Zone Request input is de-energized (Zones

Burner turns off.

are satisfied).

 

 

 

Boiler temperature drops below the Low Limit

Burner turns on and Zone Control is de-energized. Burner turns off

setting minus the differential (if applicable).

and Zone Control is re-energized when the water temperature

 

exceeds the Low Limit setting.

 

 

9

68-0281EFS—05

Page 9
Image 9
Honeywell L7224A,C, L7248A,C,L Zone Request ZR terminal is connected to, Time is applied, see Table, Minute