4.5 Alarm Signals (A)

Chapter 4 - Signals and Troubleshooting

4.5 Alarm Signals (A)

The alarm signals will be shown on the seven segment display of the control board SDCS-CON-x as codes A . . as well as on the LCD of the control panel CDP 31x as plain text. Alarm signals will only be displayed, if there is no fault signal active.

The alarm signals - with the exception of A 101 and A 102 - will not result in switching off the signal 10910 resp. in stopping the drive.

 

Code

 

 

Text on

 

Definition /

 

Signal

 

Remark

 

seven

 

 

LCD of control panel

 

Possible source

 

number

 

 

 

segm.

 

 

CDP 31x

 

 

 

(ALARM_WORD_1/2)

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A 101

 

Start inhibition

 

Alarm Start Inhibition

11104

bit 0

 

 

 

 

 

 

 

Pin 908 (START_INHIBIT) is set to logical

 

 

 

 

 

 

 

 

 

 

 

"1“; drive cannot be switched ON.

 

 

 

 

 

 

 

 

 

 

 

When pin is set to logical "0“, the alarm sig-

 

 

 

 

 

 

 

 

 

 

 

nal will be reset.

 

 

 

 

 

 

 

 

 

 

 

 

 

A 102

 

Emergency stop

 

Alarm EMERGENCY STOP

11104

bit 1

 

 

 

 

 

 

 

Pin 906 has a logical "0" level; for signal re-

 

 

 

 

 

 

 

 

 

 

 

set, see introductory remarks in Chapter 4.4

 

 

 

 

 

 

 

 

 

 

 

"Fault Signals“ and Chapter 3.7 "EMER-

 

 

 

 

 

 

 

 

 

 

 

GENCY STOP RESETTING“.

 

 

 

 

 

 

 

 

 

 

 

 

A 103

Motor 1 temp. alarm

 

Alarm Overtemperature MOTOR 1

11104

bit 2

 

 

 

 

 

 

 

Check: - Parameter setting MOT1.TEMP_

 

 

 

 

 

 

 

 

 

 

 

ALARM_L [P 1402] correct?

 

 

 

 

 

 

 

 

 

 

 

See also Fault Code F 6.

 

 

 

 

 

 

 

 

 

 

 

 

A 104

Motor 1 overl.alarm

 

Alarm Overload MOTOR 1 (Thermal Model 1)

11104

bit 3

 

 

 

 

 

 

 

Check: - See Fault Code F 7.

 

 

 

 

 

 

 

 

 

 

 

 

 

A 105

 

Conv. overtemp.

 

Alarm Overtemperature Power Section

11104

bit 4

 

 

 

 

 

alarm

 

This signal will already appear at approx.

 

 

 

 

 

 

 

 

 

 

 

10 °C below the shutdown temperature ap-

 

 

 

 

 

 

 

 

 

 

 

plying for Fault Signal F 4 (see P 10512).

 

 

 

 

 

 

 

 

 

 

 

Check: - See Fault Code F 4.

 

 

 

 

 

 

 

 

 

 

 

 

A 106

Current reg blocked

 

Alarm Current Regulator/Controller blocked

11104

bit 5

 

 

 

 

 

 

 

Pin 404 (BLOCK) is set to logical "1“.

 

 

 

 

 

 

 

 

 

 

 

When pin is set to logical "0“, the alarm sig-

 

 

 

 

 

 

 

 

 

 

 

nal will be reset.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IV A 4 - 12

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d