Chapter 4 - Signals and Troubleshooting

Code

Text on

Definition /

Status

Remark

seven

LCD of control panel

Action

signal

 

segm.

CDP 31x

 

(FAULT_WORD_1/2)

 

display

 

 

 

 

 

 

field weakening range too big / threshold too high

Check: - Do selection parameters match the field exciter (field supply)?

-Field exciter, it´s supply, cable and field winding;

-Take this error message at the data logger as a trigger condition and record signals 11302 and 11203

-Status/level of acknowledge signal.

F 40 No ext. FAN ack.

No acknowledge from FAN of motor

11102 bit 6 (1)

Check: - Was input for acknowledge signal (parameter [P 911]) used?

-Contactor circuit/supply for fan of motor;

-Status of binary inputs/outputs (DI/DO) on SDCS-IOB-1/2 board.

F 41 No main cont. ack.

Missing main contactor acknowledge

11102 bit 7

(3)

Check: - Switch-ON/-OFF sequence correct?

- Status of binary input DI for ac- knowledge signal and of ACK MAIN CONT ([P 912]) after main contactor is closed;

-Status of binary output DO resp. of auxiliary contactor (relay) closing the main contactor after ON/OFF command.

F 42 Field ex.1 not OK

FIELD EXCITER 1 (field supply 1) status is not 11102 bit 12

(1)

 

O.K.

 

Afault was found during self-diagnosis of field exciter {see [11203])}

Check: - Field exciter operation; change the unit, if necessary.

F 43 Field ex.2 not OK

FIELD EXCITER 2 (field supply 2) status is not 11102 bit 13

(1)

 

O.K.

 

 

{See Fault Code F 42}

 

DCS 500B / DCP 500B Operating Instructions

IV A 4 - 9

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Page 61
Image 61
DCS 500 manual No ext. FAN ack, No main cont. ack, Field ex.1 not OK, Field ex.2 not OK, See Fault Code F