Chapter 4 - Signals and Troubleshooting
Code | Text on | Definition / | Status | Remark |
seven | LCD of control panel | Action | signal |
|
segm. | CDP 31x |
| (FAULT_WORD_1/2) |
|
display |
|
| ||
|
|
|
|
field weakening range too big / threshold too high
Check: - Do selection parameters match the field exciter (field supply)?
-Field exciter, it´s supply, cable and field winding;
-Take this error message at the data logger as a trigger condition and record signals 11302 and 11203
-Status/level of acknowledge signal.
F 40 No ext. FAN ack. | No acknowledge from FAN of motor | 11102 bit 6 (1) |
Check: - Was input for acknowledge signal (parameter [P 911]) used?
-Contactor circuit/supply for fan of motor;
-Status of binary inputs/outputs (DI/DO) on
F 41 No main cont. ack. | Missing main contactor acknowledge | 11102 bit 7 | (3) |
Check: -
- Status of binary input DI for ac- knowledge signal and of ACK MAIN CONT ([P 912]) after main contactor is closed;
-Status of binary output DO resp. of auxiliary contactor (relay) closing the main contactor after ON/OFF command.
F 42 Field ex.1 not OK | FIELD EXCITER 1 (field supply 1) status is not 11102 bit 12 | (1) |
| O.K. |
|
Afault was found during
Check: - Field exciter operation; change the unit, if necessary.
F 43 Field ex.2 not OK | FIELD EXCITER 2 (field supply 2) status is not 11102 bit 13 | (1) |
| O.K. |
|
| {See Fault Code F 42} |
|
DCS 500B / DCP 500B Operating Instructions | IV A 4 - 9 |