DCS 500 manual Panel Functions, Actual Signal Display Mode, IV A 3

Models: 500

1 76
Download 76 pages 28.4 Kb
Page 39
Image 39
3.3 Panel Functions

3.3 Panel Functions

Actual Signal

Display Mode

ACT

Chapter 3 - Handling of Control Panel CDP 31x

The CDP 31x has four different keypad modes:

Actual Signal Display Mode (ACT)

Parameter Mode (PAR)

Function Mode (FUNC)

Drive Mode (DRIVE) for further extensions

This keypad mode will show, depending on the drive´s history:

Actual Signals

Faults

Fault History Logger

If the ACT-key is pressed immediately after initialization this table is displayed. If no panel-key is touched for more than one minute the Actual Signal Display will appear automatically, except when Status display or speed reference setting is active. (see chapter 3.13 and 3.15)

Actual Signal Display

ID-number

Control

Speed

Main contactor

Run Status

of the Drive

Location

reference

status

I = RUN

 

L = Local

rpm

0 = Open

0 = STOP

 

 

= Remote

 

1 = Closed

 

 

 

 

 

 

 

Statusrow

 

 

 

 

0 L

0.0 rpm 00

Actual Signal

 

 

 

 

 

 

SPEED AC

0.0

rpm

 

 

Name, value and unit

CONV CUR

0

A

 

 

 

 

 

Cursor shows

 

 

U ARM AC

0

V

 

 

 

 

 

 

_

 

 

 

the selected row

If a fault is effective in the drive, the Fault Display will appear auto- matically. This will happen with all other modes as well, except the Drive Mode is active.

Fault Display

 

 

 

0 L

0.0

rpm 00

 

 

 

DCS 500

 

 

 

 

 

*** FAULT ***

 

Type of fault or alarm

 

 

No ext. FAN ack.

 

 

 

 

 

 

 

 

To select Fault History Display see chapter 3.8

Fault History Display

1

= last fault

 

 

 

0

L

0.0

rpm 00

 

 

 

2

= second last fault

1

LAST FAULT

 

...

 

 

 

 

Fault or alarm name

 

I/O-Board not

found

 

Total time after

 

the power up

 

0000:14:12.64

 

 

 

 

 

 

 

HHHH:MM:SS.ss

DCS 500B / DCP 500B Operating Instructions

IV A 3 - 3

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Page 39
Image 39
DCS 500 manual Panel Functions, Actual Signal Display Mode ACT Parameter Mode PAR Function Mode FUNC, IV A 3