1201 = 5

Chapter 2 - Start-Up Instructions

Only for armature-circuit power converters with SDCS-CON-2 control board & CDP 312 panel!

1201 = 5

Panel display: FEX2/3 AUTOTUNING

Activates the field current controller's auto-tuning function.

Action has been completed when NOT ACTIVATED is shown on the display.

Switch OFF power!

11202 = SAVE MOT1 SET

Save the altered values in the non-volatile memory!

Continue with Chapter 2.4

Only for controlled field supply with DCF 501B or DCF 502B !

505 = 2Panel display: FEX2 OR FEX3

503 = Rated motor field current

Scales all parameters referenced to the motor field current, such as field cur- rent limitation or field current monitoring.

If field current is above 150A, multiply the value by 0.1 and use this number (problem: upper limit of P503 / P504) ; the reference transferred to the DCF 500B is always 100% independent of this setting; by doing so all indications on the panel CDP312 can be corrected quite easily by multiplying by 10

1305 = Field current for "Under-excitation" signal

Switch OFF power!

11202 = SAVE MOT1 SET

Save the altered values in the non-volatile memory!

Before adjustment of the armature-circuit power converter is continued (Chapters 2.4 etc.),

First perform the start-up routine for the DCF 501B or DCF 502B field supply unit (Chapter 2.9) and

then: continue with Chapter 2.4

DCS 500B / DCP 500B Operating Instructions

IV A 2 - 9