Chapter 2 -
Only for
1201 = 5 | Panel display: FEX2/3 AUTOTUNING |
Activates the field current controller's
Action has been completed when NOT ACTIVATED is shown on the display.
Switch OFF power!
11202 = SAVE MOT1 SET
Save the altered values in the
Continue with Chapter 2.4
Only for controlled field supply with DCF 501B or DCF 502B !
505 = 2Panel display: FEX2 OR FEX3
503 = Rated motor field current
Scales all parameters referenced to the motor field current, such as field cur- rent limitation or field current monitoring.
If field current is above 150A, multiply the value by 0.1 and use this number (problem: upper limit of P503 / P504) ; the reference transferred to the DCF 500B is always 100% independent of this setting; by doing so all indications on the panel CDP312 can be corrected quite easily by multiplying by 10
1305 = Field current for "Under-excitation" signal
Switch OFF power!
11202 = SAVE MOT1 SET
Save the altered values in the
Before adjustment of the
First perform the
then: continue with Chapter 2.4
DCS 500B / DCP 500B Operating Instructions | IV A 2 - 9 |
3ADW000055R0401_DCS500B_Operating Instruction_e_d