Chapter 2 - Start-Up Instructions

When the display shows NOT ACTIVATED (action correctly completed):

Stop drive

Switch OFF power!

In case the autotuning failed:

1201 = 4Panel display: ARM. MAN. TUNING

ARM.MAN_TUNING, if the FEX2/3 autotuning failed; activate the reference via pa- rameter 11209 and set the parameters of the square wave function generator; then adapt the current controller to get the behaviour shown at curve D chapter 2.6.3 in this manual

1215 = 4Panel display: FEXLINK NODE 1

DCF mode FEXLINK NODE1 via FEX-link activated

11202 = SAVE MOT1 SET

Save the altered values in the non-volatile memory!

The DCS converter in DCF-mode (parameter 1215=1 or higher) will not accept a start command, if an alarm or fault is still active (an A or F indication on the 7-segment dis- play). To ensure a correct function afterwards, please make sure the reasons for any type of alarm or fault is no longer present.

Continue with Chapter 2.4