Chapter 2 - Start-Up Instructions

2.6 Balancing the field supply unit and the e.m.f. controller

When matching the field supply unit to the system conditions, differences in the proce- dures adopted must be taken into account; these different procedures result from the op- erating mode used. Only the work of that section has to be performed which deals with the operating mode actually used in your system!

Constant field current control

⇒

Section 2.6.1

Field weakening control with setting range smaller than 1 : 1.5

⇒

Section 2.6.2

Field weakening control with setting range larger than 1 : 1.5

⇒

Section 2.6.3

2.6.1 Constant field current control

 

 

Switch ON power; start drive.

 

 

DANGER: System components now energized!

 

 

Drive should run up to 10 % of the speed.

 

 

12516 = increase slowly!

Internal reference value is increased; scaling: 20000 corresp. to 100 % speed or motor voltage, defined with P 501.

Measure motor voltage with the U ARM AC signal by changing between MODE ACT and PAR; with a value set with P 501, it must remain constant, or must not exceed this value if 12516 = 20000.

The motor voltage must not exceed the recommended motor voltage; see General notes at the beginning of this chapter.

Measure speed with manual tacho;

check rated speed when an analog tacho is being used; if necessary, correct with R9, R48 or R2716.

12516 = 0

Switch OFF power, thus stopping the drive!

Continue with Chapter 2.7

IV A 2 - 14

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Page 26
Image 26
DCS 500 manual Balancing the field supply unit and the e.m.f. controller, Continue with Chapter