DCS Signals and Troubleshooting, DCS 500B / DCP 500B Operating Instructions, IV A 4, S21.232

Models: 500

1 76
Download 76 pages 28.4 Kb
Page 65
Image 65

Chapter 4 - Signals and Troubleshooting

 

Code

 

 

Text on

 

Definition /

 

Signal

 

Remark

 

seven

 

 

LCD of control panel

 

Possible source

 

number

 

 

 

segm.

 

 

 

 

 

CDP 31x

 

 

 

(ALARM_WORD_1/2)

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A 108

RAM-backup failed

 

Alarm No Battery Backup Function for RAM

11104

bit 7

 

 

 

 

 

 

 

Capacitor for RAM backup has discharged

 

 

 

 

 

 

 

 

 

 

 

(perhaps unit has been stored for too long

 

 

 

 

 

 

 

 

 

 

 

without the electronics voltage switched

 

 

 

 

 

 

 

 

 

 

 

on?); load capacitor by leaving unit electron-

 

 

 

 

 

 

 

 

 

 

 

ics switched on for a lengthy period.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A 110

System restart

 

Alarm System Restart

 

 

 

 

 

 

 

 

 

 

 

Signal is filed in fault memory (fault logger),

 

 

 

 

 

 

 

 

 

 

 

but not displayed at the unit or the LC-

 

 

 

 

 

 

 

 

 

 

 

Display of the CDP 31x.

 

 

 

 

 

 

 

 

 

 

 

 

A 118

Mains underv.alarm

 

Alarm Mains Undervoltage (AC)

11104

bit 10

 

 

 

 

 

 

 

Setting of undervoltage monitoring with Pa-

 

 

 

 

 

 

 

 

 

 

 

rameter [P 508]

 

 

 

 

 

 

 

 

 

 

 

Check: - See also Fault Code F 29.

 

 

 

 

 

 

 

 

 

 

 

 

A 120

Arm.curr.dev.alarm

 

Alarm Armature Current Deviation

11104

bit 13

 

 

 

 

 

 

 

If the current reference [P 10405] deviates

 

 

 

 

 

 

 

 

 

 

 

from the current feedback for more than

 

 

 

 

 

 

 

 

 

 

 

5 sec by more than 20 %, referenced to the

 

 

 

 

 

 

 

 

 

 

 

rated current, this signal will be outputted.

 

 

 

 

 

 

 

 

 

 

 

 

A 121

Ext.Overvolt.Alarm

 

Overvoltage protection DCF 506 has acted

11105

bit 6

 

 

 

 

 

 

 

There was an overvoltage condition in the

 

 

 

 

 

 

 

 

 

 

 

DC circuit of the field supply, which had been

 

 

 

 

S21.232

 

 

 

 

 

 

limited by the activation of a free wheeling

 

 

 

 

and

 

 

 

 

 

 

circuit.

 

 

 

 

higher

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check: - Power wiring of the field supply

 

 

 

 

 

 

 

 

 

 

 

- Control logic according to wiring

 

 

 

 

 

 

 

 

 

 

 

example?

 

 

 

 

 

 

 

 

 

 

 

- Does PP_DI_OVP [1216] has been

 

 

 

 

 

 

 

 

 

 

 

connected to a binary input?

 

 

 

 

 

 

 

 

 

 

 

- Setting of OVP_SELECT [1217]

 

 

 

 

 

 

 

 

 

 

 

correct? (see Fault 121)

 

 

 

 

 

 

 

 

 

 

 

 

A 123

Motor 2 temp. alarm

 

Alarm Overtemperature MOTOR 2

11104

bit 8

 

 

 

 

 

 

 

Check: - Parameter setting MOT2.TEMP_

 

 

 

 

 

 

 

 

 

 

 

ALARM_L [P 1602] correct?

 

 

 

 

 

 

 

 

 

 

 

See also Fault Code F 6.

 

 

 

 

 

 

 

 

 

 

 

 

A 124

Motor 2 overl alarm

 

Alarm Overload MOTOR 2 (Thermal Model 2)

11104

bit 9

 

 

 

 

 

 

 

Check: - See Fault Code F 7.

 

 

 

 

 

 

 

 

 

 

 

 

 

A 126

 

Conv.FAN ack.alarm

 

Alarm No (Thyristor Power) Converter FAN

11104

bit 12

 

 

 

 

 

 

 

Acknowledge

 

 

 

 

 

 

 

 

 

 

 

Check: - See Fault Code F 50.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCS 500B / DCP 500B Operating Instructions

 

 

IV A 4 - 13

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Page 65
Image 65