Chapter 4 - Signals and Troubleshooting
| Code |
|
| Text on |
| Definition / |
| Signal |
| Remark | |
| seven |
|
| LCD of control panel |
| Possible source |
| number |
|
| |
| segm. |
|
| ||||||||
|
|
| CDP 31x |
|
|
| (ALARM_WORD_1/2) |
|
| ||
| display |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||
A 108 |
| Alarm No Battery Backup Function for RAM | 11104 | bit 7 |
| ||||||
|
|
|
|
|
| Capacitor for RAM backup has discharged |
|
|
|
|
|
|
|
|
|
|
| (perhaps unit has been stored for too long |
|
|
|
|
|
|
|
|
|
|
| without the electronics voltage switched |
|
|
|
|
|
|
|
|
|
|
| on?); load capacitor by leaving unit electron- |
|
|
|
|
|
|
|
|
|
|
| ics switched on for a lengthy period. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
A 110 | System restart |
| Alarm System Restart |
|
|
|
|
| |||
|
|
|
|
|
| Signal is filed in fault memory (fault logger), |
|
|
|
|
|
|
|
|
|
|
| but not displayed at the unit or the LC- |
|
|
|
|
|
|
|
|
|
|
| Display of the CDP 31x. |
|
|
|
|
|
|
|
|
|
|
|
| |||||
A 118 | Mains underv.alarm |
| Alarm Mains Undervoltage (AC) | 11104 | bit 10 |
| |||||
|
|
|
|
|
| Setting of undervoltage monitoring with Pa- |
|
|
|
|
|
|
|
|
|
|
| rameter [P 508] |
|
|
|
|
|
|
|
|
|
|
| Check: - See also Fault Code F 29. |
|
|
|
|
|
|
|
|
|
|
|
| |||||
A 120 | Arm.curr.dev.alarm |
| Alarm Armature Current Deviation | 11104 | bit 13 |
| |||||
|
|
|
|
|
| If the current reference [P 10405] deviates |
|
|
|
|
|
|
|
|
|
|
| from the current feedback for more than |
|
|
|
|
|
|
|
|
|
|
| 5 sec by more than 20 %, referenced to the |
|
|
|
|
|
|
|
|
|
|
| rated current, this signal will be outputted. |
|
|
|
|
|
|
|
|
|
|
|
| |||||
A 121 | Ext.Overvolt.Alarm |
| Overvoltage protection DCF 506 has acted | 11105 | bit 6 |
| |||||
|
|
|
|
|
| There was an overvoltage condition in the |
|
|
|
|
|
|
|
|
|
|
| DC circuit of the field supply, which had been |
|
|
|
| S21.232 |
|
|
|
|
|
| limited by the activation of a free wheeling |
|
|
|
| and |
|
|
|
|
|
| circuit. |
|
|
|
| higher |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| Check: - Power wiring of the field supply |
|
|
|
|
|
|
|
|
|
|
| - Control logic according to wiring |
|
|
|
|
|
|
|
|
|
|
| example? |
|
|
|
|
|
|
|
|
|
|
| - Does PP_DI_OVP [1216] has been |
|
|
|
|
|
|
|
|
|
|
| connected to a binary input? |
|
|
|
|
|
|
|
|
|
|
| - Setting of OVP_SELECT [1217] |
|
|
|
|
|
|
|
|
|
|
| correct? (see Fault 121) |
|
|
|
|
|
|
|
|
|
|
|
| |||||
A 123 | Motor 2 temp. alarm |
| Alarm Overtemperature MOTOR 2 | 11104 | bit 8 |
| |||||
|
|
|
|
|
| Check: - Parameter setting MOT2.TEMP_ |
|
|
|
|
|
|
|
|
|
|
| ALARM_L [P 1602] correct? |
|
|
|
|
|
|
|
|
|
|
| See also Fault Code F 6. |
|
|
|
|
|
|
|
|
|
|
|
| |||||
A 124 | Motor 2 overl alarm |
| Alarm Overload MOTOR 2 (Thermal Model 2) | 11104 | bit 9 |
| |||||
|
|
|
|
|
| Check: - See Fault Code F 7. |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
A 126 |
| Conv.FAN ack.alarm |
| Alarm No (Thyristor Power) Converter FAN | 11104 | bit 12 |
| ||||
|
|
|
|
|
| Acknowledge |
|
|
|
|
|
|
|
|
|
|
| Check: - See Fault Code F 50. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| DCS 500B / DCP 500B Operating Instructions |
|
| IV A 4 - 13 |