2.2 Scaling intra-unit signals

Chapter 2 - Start-Up Instructions

2.2 Scaling intra-unit signals

Make sure that the existing electronics supply voltage has been set on the SDCS- POW-1 power supply board as well, using the SW1 switch.

If an encoder is being used as the speed feedback device, make sure that the correct supply voltage has been seton the boards

SDCS-POW-1: X3: / X4: / X5:

SDCS-IOB-3: S4

 

 

Switch on the power supply to the electronics section.

The display of Panel CDP 31x

DCS 500

may show the following

** WARNING **

information:

+Emergency stop

 

 

522 = GERMAN [Only with the SDCS-CON-2 control board & the CDP 312 panel!] Activates German texts on the display

501 = Rated motor voltage

This is used to scale those parameters referring to the rated motor voltage, such as field crossover point or maximum speed with e.m.f. control.

502 = Rated motor current

This is used to scale those parameters referring to the rated motor current, such as current limitation or torque limitation.

507 = Rated line voltage

This is used to scale those parameters referring to the line voltage, such as line undervoltage.

Only when connection diagram 1 (Appendix A) is being used!

906 = 12502

„Emergency Stop“ de-activated

910 = 10908

No check-back signal from unit fan necessary

911 = 10908

No acknowledge signal from motor fan necessary

Set this only for units with a rated current 2050A!

517

= Rated power converter current

 

Enter numerical value from rating plate here

518

= Rated power converter supply voltage

Enter numerical value from rating plate here

519

= 45 Grad Celsius

 

Temperature monitoring of power section

520

= 4 Size C4 has been selected

 

Coding for unit type

 

521

= 1 : Single bridge (2-Q) converter

on rating plate: DCS 501 xxxx

 

4 : Double bridge (4-Q) converter

on rating plate: DCS 502 xxxx

Coding for power section (bridge) type