DCS 500 Signals and Troubleshooting, At Macro x, macro-specific links or function, been changed

Models: 500

1 76
Download 76 pages 28.4 Kb
Page 68
Image 68
Signal

Chapter 4 - Signals and Troubleshooting

Code

Text on

Definition /

Signal

Remark

seven

LCD of control panel

Possible source

number

 

segm.

CDP 31x

 

(ALARM_WORD_1/2)

 

display

 

 

 

 

 

 

A 143 Macro change failed Alarm Change from Macro x to Macro y has

11105 Bit 7

failed

 

At Macro x, macro-specific links or function

S21.226

blocks have been changed in comparison

and

to the as-delivered status. The value of the

higher

macro selection parameter has then also

 

been changed.

 

Notes on how to proceed when:

1."selection parameter has been unintentionally altered"

-Set parameter to old value;

-Execute BACKUPSTOREMODE;

-Switch electronics supply OFF and then ON again.

2."Macro x is be removed in its entirety"

-Move jumper S2 (on SDCS-CON-x) to Position 1–2 with electronics supply switched OFF;

-Switch ON electronics;

-Select BACKUPSTOREMODE [11202];

-Save default parameter set;

-Switch OFF electronics;

-Reset jumper S2 to its original position;

-Switch ON electronics again.

IV A 4 - 16

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Page 68
Image 68
DCS 500 Signals and Troubleshooting, At Macro x, macro-specific links or function, blocks have been changed in comparison