Chapter 4 - Signals and Troubleshooting

Code

Text on

Definition /

Status

Remark

seven

LCD of control panel

Action

signal

 

segm.

CDP 31x

 

(FAULT_WORD_1/2)

 

display

 

 

 

 

 

 

F 3

Conv.fan curr.fault

Current converter fan not within limits

11103 bit 11

(1)

The current of the converter´s cooling fan is

 

measured via the option board PW1002/3.

S21.232

Check: - Fan supply, fan current;

- Setting of PW1002,

and

higher

SET_MAX_BR_TEMP [P519] and

 

CONV_TEMP_DELAY [P527]

 

-Direction of rotation, fan compo nents, air inlet

F 4 Converter overtemp. Overtemperature power section

11101 bit 3

(2)

Check: - Fan supply, direction of rotation, fan components, air inlet and ambient temperature;

- Inadmissible load cycle?

F 5

Earth fault

Earth fault (Σ I differs from zero)

11101 bit 4

(1)

Disconnect the mains and verify zero voltage in armature and field circuits.

Make insulation test for the complete installation.

Check sum current transformer; if necessary, change transformer and SDCS-IOB-3 board.

F 6 Motor 1 overtemp.

Overtemperature of MOTOR 1

11101 bit 5 (2)

Check: - Temperature sensor and its cabling;

-Motor cooling or sizing;

-Inputs for temperature sensor on board SDCS-IOB-3;

-Parameter setting MOT1.TEMP_

FAULT_L [P 1403] correct?

Note: It will only be possible to reset this fault signal when the motor temperature has fallen below the threshold which is valid for the alarm signal A 103; the signal will also be evaluated while the mains contactor is de-energized (open).

F 7 Motor 1 overload

Overload of MOTOR 1 (Thermal model 1)

11101 bit 6

(2)

 

Check: - Motor temperature (let motor cool

 

 

 

down and restart);

 

 

-Motor ratings and parameters of thermal model;

-Motor sizing or load cycle.

IV A 4 - 4

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Page 56
Image 56