Honeywell PGF3 Important Information, Installation, Explosion Hazard, Gas Pressures

Models: PGF3

1 7
Download 7 pages 61.19 Kb
Page 2
Image 2
Important Information

Important Information

This kit includes a Honeywell conversion kit for converting Honeywell VR8200, VR8205S, SV9500, SV9501 or VR8204M gas valves certified for use with Propane Gas (and so marked) to units functionally the same as the certified furnace for use with Natural Gas. If converting from propane gas to natural gas, the gas valve conversion kit, main burner orifices, and pilot orifice, all found in this kit, must be installed.

For converting the furnace from standard altitude on natural gas to high altitude (2001 feet above sea level or greater) on natural gas, the Honeywell conversion kit and pilot orifice changes are not needed. Only the main burner orifices require changing. Refer to Table 1 for proper orifice size for specific model number, input capacity, and installation altitude.

The orifices provided in this kit are stamped to indicate the size (twist drill number) and are sized for natural gas ONLY. Do NOT use them with butane or a mixture of butane and propane. The parts list specifies the size orifices supplied in the kit. Compare the size marking on the orifices with the sizes as listed in the parts list. Make sure you have the correct main burner orifices.

Extreme care is used to assure that this kit contains the proper orifices. Oversized orifices could result in hazardous conditions, especially if the venting is inadequate. For that reason, we recommend that the installer check the size of the orifice with a new twist drill of the correct size. This procedure assures that the orifices provided are the correct size.

!

ELECTRIC SHOCK HAZARD/FIRE AND/OR EXPLOSION HAZARD.

Failure to follow this warning could result in equipment damage, personal injury, death and/or property damage.

The gas supply shall be shut OFF prior to disconnecting the electrical power, before proceeding with the conversion.

Turn OFF electric power supply at disconnect switch or service panel before starting installation.

DShut off gas supply to furnace at manual shut--off valve be- fore starting installation.

!

EXPLOSION HAZARD

Failure to follow this warning could result in personal injury, death and/or property damage.

If unit is still running, allow 2.5 minutes after gas shut off before turning off power, Shut Off electric power at unit disconnect and service panel.

DDisconnect electric power supply to the furnace before starting installation.

DCheck for gas leaks after installation of kit and before at- tempting to start furnace.

DLocate the Natural Gas Conversion Label next to the fur- nace rating plate.

DFill out and attach the Field Conversion Label to the front ex- terior of the furnace.

!ELECTRIC SHOCK HAZARD/FIRE AND/OR EXPLOSION HAZARD.EXPLOSION HAZARDFIRE, EXPLOSION, CARBON MONOXIDE POISONING HAZARD.Gas PressureGas PressuresInstallation

FIRE, EXPLOSION, CARBON MONOXIDE POISONING HAZARD.

Failure to follow these instructions exactly could result in personal injury, death and/or property damage.

This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, an explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.

Gas Pressure

DRefer to the furnace rating plate for the approved gas input rating.

DGas input to burners MUST NOT exceed the rated input shown on rating plate.

DDo NOT allow minimum gas supply pressure to vary down- ward. Doing so will decrease input to furnace. Refer to Table 2 for gas supply and manifold pressures.

Table 2

 

Gas Pressures

 

 

 

 

 

Gas

 

Supply Pressure

 

Manifold

Type

 

 

 

Pressure

Recommended

Max.

Min.

 

 

 

 

 

Natural

7″

13″

4.5″

3.5″

Installation

!

ELECTRIC SHOCK HAZARD/FIRE AND/OR EXPLOSION HAZARD.

Failure to follow this warning could result in property damage, equipment damage, personal injury and/or death.

Turn OFF gas supply at manual gas valve before turning OFF electric power supply and starting installation.

Turn OFF electric power supply at disconnect switch or service panel before starting installation.

 