e)Supervisory Main: 192.168.0.1 (note this is the primary receiver’s IP address assigned by central station)

f)Supervisory Backup: 192.168.0.2 (note this is the secondary receiver’s IP address assigned by central station.)

g)Maintenance: This is a third IP receiver setting that is not normally used. A third maintenance receiver can be installed at a remote site and used to obtain trouble signals such as at a maintenance facility or dealer location.

h)Port: (80 is the default but the central station may assign a different one)

DO NOT REGISTER the IPDACT at this point. PROCEED to the next step - RESET.

j)(Select item “j” Reset). At this point the IPDACT will reset and prompt for the default password. This step fixes the programming you entered into the flash memory of the IPDACT.

Enter password 24680 and press the enter key.

Enter password 24680 when prompted again. You should see

“PASSWORD ACCEPTED”

At the menu options screen, once again select "c: Quick Install"

i)(Select i) Register MIP

When prompted for password Use the different installation password assigned by Central such as: 1111 you should see “OK” in the display if successful. Check that LED "LD6" is illuminated - this indicates proper communication/registration with the CS receiver.

Note: If you do not see OK, it could be that the Account Number has already been registered with the receiver by another IPDACT. If you see the message VA unreachable, recheck all the given parameters and be sure to use the different installation password assigned by the Central Station, NOT the default of 24680!

z)Select z) to exit submenu Select z again to exit to main menu

Close HyperTerminal

Disconnect your serial cable from the PC and the IPDACT.

Ensure the FACP is programmed for DACT communications as if you were using standard phone line connections with the following information. Remember the

5/19/2008

12 of 15

Page 12
Image 12
Honeywell Smoke Alarm installation instructions Select i Register MIP