Honeywell Smoke Alarm installation instructions Connect serial cable here CN1

Models: Smoke Alarm

1 15
Download 15 pages 48.03 Kb
Page 4
Image 4
Connect serial

4.Loop the 8 PIN cable supplied with the IPDACT once through the large Ferrite Ring. Note that this cable is NOT used as an Ethernet Cable but to interconnect the dialer output of the panel to the input of the IPDACT. Plug the 8 PIN cable supplied with the IPDACT into the Primary DACT port of the control panel. Connect the other end of this cable to he IPDACT on terminals marked 'TO AP."

5.Connect the secondary DACT port of the control panel to a standard unpublished RJ-31X phone jack. Note that if the secondary port on the FACP is not used for a backup via POTS line, the IPSPLT can be obtained and used to combine both phone lines. In this case, the cable supplied with the IPDACT connects to the single connector on the IPSPLT (See Panel Manual).

Connect serial

cable here

(CN1)

6.Plug one end of the IPDACT Programming Cable (PN ALSMSC120 (shown above or equivalent) into the black RJ45 receptacle on the IPDACT labeled CN1. Plug the other end of this cable into the supplied RS-232 serial adapter that came with the black cable. Plug the adapter into a COM port on your computer.

7.Connect one end of a CAT5 LAN cable into the Ethernet receptacle on the IPDACT as shown below (Green cable) and the other end into an available port on the customer’s LAN hub or switch.

5/19/2008

4 of 15

Page 4