Honeywell SN0500 manual Standard Default Settings

Models: SN0500

1 8
Download 8 pages 24.67 Kb
Page 6
Image 6
7. STANDARD DEFAULT SETTINGS

GAS LEAK DETECTOR INSTALLATION & USER GUIDE

7. STANDARD DEFAULT SETTINGS

Relay 1 Low-level relay set at 500 PPM, NO, Auto reset mode

Relay 2 High-level relay set at 900 PPM, NO, Auto reset mode.

Delays on both alarm outputs are 0 minutes (no delay).

CON 1: Power Supply input Power on indicated by Green LED.

Supply voltages to be either 12V to 24V AC or 12 to 30V DC Power consumption is 4W max at 12V.

The connectors will accept wire of 0.5-1.5mm² Refer to Section 3 for maximum cable run.

CON 2: Not Used.

CON 3: Analogue Output

Pin 1: 0V

Pin 2: 4-20mA. Load resistance<400Ω

Pin 3:0-10V. Load resistance>100Ω

Pin 4: 0-5V. Load resistance>10KΩ

CON 4: Plug-in detection sensor

CON 5: Not Used

CON 6: Relay 1 contacts (1Amp 24V AC/DC) Low-level alarm. Indicated by Yellow LED.

Normally closed when JP4 link inserted, JP3 link removed, as shown on Fig. 1. Normally open when JP3 link inserted, JP4 link removed, as shown on Fig. 1. Latching (manual reset by push button located next to CON 7) / Not Latching set by JP8 (see Fig. 1. in Connection Instructions)

Alarm Threshold level set by RV1 and can be set by putting a meter between TP0 (negative) and TP2 (positive) and adjusting RV1 (scale is 0 to 5V e.g. 2.5V is 50% of scale).

Delayed response time set by JP1 link (see Fig. 1. in External Connections)

Position 1= No delay

Position 3=5 min

Position 2=1 min

Position 4=10 min

CON 7: Relay 2 contacts (1Amp 24V AC/DC) High-level alarm. Indicated by Red LED on.

Normally open/closed when JP5 link inserted, as shown on Fig. 1.

Latching (manual reset by push button located next to CON 7) / Not Latching set by JP7 (as above)

Alarm threshold level set by RV2 and can be set by putting a meter between TP0 (negative) and TP3 (positive) and adjusting RV2 (scale is 0 to 5V e.g. 2.5V is 50% of scale).

Delayed response time is set by JP2 link (see Fig. 1. in External Connections).

Position 1= No delay

Position 3=5 min

Position 2=1 min

Position 4=10 min

If changing any jumper - power must be removed.

EN1B-0014UK07 R0404

6

Page 6
Image 6
Honeywell SN0500 manual Standard Default Settings