Electrical One-Line Drawing Part 2

SHEET NOTES

1FOR ROOF MOUNT TURBINE, LOCAL FIRE DEPARTMENTS MAY REQUIRE DC DISCONNECTS AT THIS LOACTION. IF REQUIRED, PROVIDE SQUARE D H221NRB

2LOCATE BESIDE OR BENEATH CONTROLLER

3LOCATE OUTSIDE OR IN WELL VENTILATED AREA

!4 LOCATE AND BOLT FUSE ON BATTERY POSITIVE TERMINAL

EQUIPMENT SCHEDULE

TAG

EQUIPMENT MANUFACTURE

EQUIPMENT DESCRIPTION

MODEL / PART NO

1

WINDTRONICS

WIND TURBINE

NA

2

WINDTRONICS

TURBINE INTERCONNECT ENCLOSURE

NA

3

Square D

`

H221NRB

H.D. 30AMP 250VDC FUSED DISCONNECT

4

ANY

15A 250VDC FAST ACTING FUSE CLASS RK1

NA

5

WINDTRONICS

TURBINE CONTROLLER

NA

6

NA

BATTERY ENCLOSURE

NA

7

NA

BATTERY DISCONNECT

NA

8

LITTELFUSE

100AMP 24V BATTERY FUSE

0298100

9

NA

`

NA

2- 12V DEEP CYCLE BATTERIES

10

SQUARE D

`

DU221RB

G.D. 30AMP 240VAC UNFUSED DISCONNECT

11

ANY

14AWG` 1-PAIR UNSHIELDED

NA

12

ANY

`

CAT5E

CAT5E COMMUNICATION CABLE

13

ANY

`

ANY

GROUND STAKE AND CLAMP

NEC CALCULATIONS

ALL AMPACITIES CALCULATED AT 75DEG C FOR TERMINATIONS

DC VOLTAGE

TURBINE Voc = 170VDC

MAXIMUM DC VOLTAGE = 170VDC

TURBINE SOURCE CIRCUIT

TURBINE Isc = 20A (Short Circuit)

TURBINE Imp = 12.9 A (at Max Power)

SOURCE CIRCUIT OUTDOOR WIRING TO INVERTER = #10AWG USE-2/RHW-2 OR THWN-2, 90DEG RATED

TEMPERATURE CORRECTION FACTOR FOR 70DEG C AMBIENT = 0.58

TOTAL CURRENT CARRYING CONDUCTORS = 3, FACTOR = 1

CORRECTED AMPACITY = 40A X 0.58 X 1 = 23.2 A > 20 A

OUTPUT CIRCUIT OVERCURRENT PROTECTION = 15A

90% OF OVER CURRENT PROTECTION RATING = 15 X 0.90 = 13.5A OUTPUT CIRCUIT CONTINUOUS CURRENT = 12.9A < 13.5A

AC OUTPUT CIRCUIT

MAX CONTINUOUS CURRENT = 12.5A

MAX INSTANTANEOUS CURRENT = 14.37A (3 MIN)

CONTROLLER OUTPUT CIRCUIT OVERCURRENT PROTECTION = 15 A BREAKER 90% OF OVERCURRENT PROTECTION RATING = 20 X 0.90 = 13.5A

OUTPUT CIRCUIT CONTINUOUS CURRENT = 13.5A < 15A

CONTROLLER OUTPUT WIRING TO POINT OF INTERCONNECTION = #12 THWN-2 90DEG C RATED

TEMPERATURE CORRECTION FACTOR FOR 40DEG C AMBIENT = 0.88

TOTAL CURRENT CARRYING CONDUCTORS = 3, FACTOR = 1

TOTAL INVERTER INSTANTANEOUS CURRENT = 14.37A

CORRECTED AMPACITY = 25A X 0.88 X 1 = 22A >14.37A

AC INPUT CIRCUIT

MAX CONTINUOUS CURRENT = 12.5A

CONTROLLER OUTPUT CIRCUIT OVERCURRENT PROTECTION = 15 A BREAKER 90% OF OVERCURRENT PROTECTION RATING = 15 X 0.90 = 13.5A

OUTPUT CIRCUIT CONTINUOUS CURRENT = 12.5A < 13.5A

CONTROLLER OUTPUT WIRING TO POINT OF INTERCONNECTION = #12 THWN-2 90DEG C RATED

TEMPERATURE CORRECTION FACTOR FOR 40DEG C AMBIENT = 0.88

TOTAL CURRENT CARRYING CONDUCTORS = 3 FACTOR = 1

TOTAL INVERTER INSTANTANEOUS CURRENT = 12.5A

CORRECTED AMPACITY = 25A X 0.88 X 1 = 22A >12.5A

BATTERY INPUT\CHARGE CIRCUIT

MAX CONTINUOUS SOURCE INVERTER CURRENT = 72A

MAX CONTINUOUS CHARGER CURRENT = 50A; 60A PEAK 5 minuets

BATTERY CIRCUIT OVERCURRENT PROTECTION = 100 A FUSE 80% OF OVERCURRENT PROTECTION RATING = 100 X 0.80 = 80A

BATTERY CIRCUIT CONTINUOUS CURRENT = 72A < 80A

BATTERY CIRCUIT TO CONTROLLER = #4 THWN-2 90DEG C RATED

TEMPERATURE CORRECTION FACTOR FOR 40DEG C AMBIENT = 0.88

TOTAL CURRENT CARRYING CONDUCTORS = 2 FACTOR = 1

HONEYWELL™ Wind Turbine WT6500 Owner’s Manual - Rev 10

Page 44