b) Connection to a Closed Loop System

b) Connection to a Closed Loop System

Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 1/4" nominal

ID copper water tubing or equivalent is required for the condenser water supply line.

Condenser return outlet is 3/8" FPT. A minimum of 1/4" nominal ID copper water tubing or equivalent is required for the condenser return line.

Shut-off valves and drain valves should be installed at both the condenser water supply inlet and condenser return outlet.

The water supply to the condenser should not drop below 4 GPM.

The pressure differential between the condenser water supply inlet and condenser return outlet must be no less than 10 PSIG.

When using a glycol blend, the solution mixture should be less than 30% glycol.

In order to maintain the proper high side pressure, the condenser water supply inlet temperature should not drop below 45°F (7°C) and the condenser drain outlet temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation

is complete, confirm the condenser drain outlet temperature 5 minutes after a freeze cycle starts. If the condenser drain outlet temperature is not in the proper range, use a flat blade screwdriver to rotate the adjustment screw on the water‑regulating valve until the temperature is in the proper range (rotate counterclockwise to raise temperature or clockwise to lower temperature).

Storage Bin

Drain Outlet

3/4" FPT

Drip Tray

Drain Outlet

3/4" FPT

Fig. 6

 

 

Minimum 1/4" Nominal ID

 

 

 

Icemaker

Copper Water Tubing

 

 

 

 

Icemaker Water Supply

 

 

Line Shut-Off Valve

 

Icemaker Water

 

 

 

 

Supply Inlet

 

 

 

 

1/2" FPT

 

 

Icemaker Water Supply

 

 

 

 

 

 

 

 

Line Drain Valve

 

Condenser

 

 

Condenser Return

 

Return Outlet

 

 

 

3/8" FPT

 

 

Line Shut-Off Valve

 

 

 

 

Condenser Water Supply

 

 

 

 

Line Shut-Off Valve

 

 

 

Condenser Return

 

 

 

Line Drain Valve

 

 

 

Condenser Water Supply

 

 

 

Line Drain Valve

Stand

 

Condenser Water

 

Separate piping to approved

 

Supply Inlet

 

Vent

 

drain. Leave a 2-inch (5‑cm)

 

1/2" FPT

 

 

Tube

 

vertical air gap between the

 

 

 

 

end of each pipe and the

 

 

 

 

drain.

 

 

 

 

2-inch (5-cm)

 

 

 

 

air gap

Minimum 3/4" Nominal ID

 

 

 

Hard Pipe

 

 

 

 

 

DCM-751BWH(-OS)

 

 

Connection to a Closed Loop System

Floor Drain

 

 

 

 