6.Water Supply and Drain Connections See Fig. 3

6.Water Supply and Drain Connections See Fig. 3

External filters, strainers or softeners may be required depending on the water quality.

Water supply inlet is 1/2" female pipe thread (FPT).

A water supply line shut-off valve and drain valve should be installed. A minimum of 3/8" OD copper tubing is recommended for the water supply lines.

Water supply pressure should be a minimum of 10 PSIG and a maximum of 113 PSIG. If the pressure exceeds 113 PSIG, the use of a pressure reducing valve is required.

Drain outlet for icemaking is 3/4" FPT. The icemaker drain piping connection must be made separately from the bin drain.

The drains must have 1/4" fall per foot on horizontal runs to get a good flow.

The drains should not be piped directly to the sewer system. An air gap of a minimum of 2 vertical inches should be between the end of the drain pipe from the icemaker or the ice bin and the floor drain.

A plumbing permit and services of a licensed plumber may be required in some areas.