The maximum freeze timer is VR3. This timer will automatically switch the unit to the harvest cycle if the freeze cycle last longer than the setting time. The factory setting is 45 minutes.

10

The maximum freeze timer is VR3. This timer will automatically switch the unit to the harvest cycle if the freeze cycle last longer than the setting time. The factory setting is 45 minutes.

The defrost control VR2 will adjust the time period between ice-drop and actuator motor restart during harvest. The factory setting is 4. This setting represents approximately 40 seconds. VR2 would be adjusted longer if the unit is operating in a cooler ambient temperature.

The control board includes a push- button reset. Pressing this button will initiate a harvest cycle anytime the control switch is in ICE position.