N. Adjustment Of Water Regulating Valve –
The water regulating valve (also called "water regulator") is
1)Attach a pressure gauge to the
2)Rotate the adjustment screw by using a flat blade screwdriver, so that the pressure gauge shows 270 PSIG or the thermometer reads 104 to 115°F, 5 minutes after a freeze cycle or icemaking process starts. When the pressure exceeds 270 PSIG, or the condenser drain temperature exceeds 115°F, rotate the adjustment screw counterclockwise. See Fig. 2.
3)Check that the pressure or the condenser drain temperature holds a stable setting.
Adjustment Screw | Adjustment Screw |
CW – Higher
CCW – Lower
Top View
Fig. 2
44