2. Condensing Unit

IMPORTANT

This condensing unit is intended for outdoor use. Normal operating ambient temperature should be within -20°F to +122°F (-29°C to 50°C). Operation of the unit, for extended periods, outside of these normal temperature ranges may affect icemaker performance.

The icemaker must be coupled with the appropriate condensing unit as listed below.

Icemaker

Hoshizaki Condensing Unit

 

 

KMS-1400MLH

SRK-14H/3

The condensing unit must be positioned in a permanent site under the following guidelines:

A firm and flat site.

A dry and well ventilated area with 24" (61 cm) clearance in both front and rear for proper air circulation and ease of maintenance and/or service should they be required. See Fig. 1.

The maximum line length is 55 feet.

Note: If the recommended guidelines of the installation are exceeded, the icemaker performance may be reduced.

CAUTION

Failure to install the equipment within these guidelines may adversely affect performance, component life, and warranty coverage.

Minimum 24" (61 cm) Clearance

AirAir

Fig. 1