Hoshizaki KMS-1400MLH instruction manual E. Installation of the Condensing Unit, Line Set, Setup

Models: KMS-1400MLH

1 29
Download 29 pages 26.79 Kb
Page 16
Image 16
E. Installation of the Condensing Unit

E. Installation of the Condensing Unit

CAUTION

1.Failure to install the equipment within these guidelines may adversely affect performance, component life, and warranty coverage

2.Power supply and ground wire to the icemaker are supplied from the condensing unit. For details, see section "II.F. Electrical Connection."

1.Setup

1)Secure the condensing unit to the stand with sixteen M8×16 mm hexagon bolts and M8 nuts as shown in the illustration. See Fig. 4.

2)The legs have eight mounting holes. Secure the legs with eight bolts (not included).

3)See the nameplate on the condensing unit. Check that your voltage supplied corresponds with the voltage specified on the nameplate.

WARNING

Electrical connections must be made in accordance with national, state, and local regulations. See "II.F. Electrical Connection."

M8x16mm Bolt

M8 Nut

Fig. 4

2.Line Set

Precharged tubing kits, available as optional equipment from HOSHIZAKI AMERICA, are recommended. Field fabricated line sets are allowed, see instructions below.

The maximum line length is 55 feet.

Vertical distance between the condensing unit and icemaker should not exceed 30 feet above or 10 feet below the icemaker.

If the vertical distance between the condensing unit and the icemaker is greater than 18 feet, a p-trap (5/8" OD tubing) must be installed in the suction line. The p-trap must be within 18 vertical feet of both the condensing unit and the icemaker. This will ensure sufficient oil return to the compressor.

16

Page 16
Image 16
Hoshizaki KMS-1400MLH instruction manual E. Installation of the Condensing Unit, Line Set, Setup