QuickSpecs

HP ProLiant DL380 Generation 7 (G7)

Power Specifications

HP 1200W Common Slot Platinum Hot Plug Power Supply Kit

Part Number

578322-B21

 

 

 

 

 

 

 

 

Input Voltage Range ( V rms )

100 to 240

 

 

 

 

 

 

 

 

Frequency Range (Nominal) ( Hz )

50/60

 

 

 

 

 

 

 

 

 

 

Nominal Input Voltage ( Vrms )

100

 

120

200

208

220

 

230

 

240

Maximum Rated Output Wattage Rating

800

 

900

1200

1200

1200

1200

 

1200

Nominal Input Current ( A rms )

9.3

 

8.6

6.7

6.5

6.1

 

5.8

 

5.6

Maximum Rated Input Wattage Rating ( Watts )

889

 

989

1290

1290

1290

1290

 

1290

Maximum Rated VA ( Volt-Amp )

927

 

1031

1345

1345

1345

1345

 

1345

Efficiency ( % )

90

 

91

93

93

93

 

93

 

93

Power Factor

 

 

 

 

 

0.97

 

 

 

 

 

Leakage Current ( mA )

0.42

 

0.50

0.83

0.87

0.92

0.96

 

1.00

Maximum Inrush Current ( A peak )

 

 

 

 

 

30

 

 

 

 

 

Maximum Inrush Current duration ( mS )

 

 

 

 

 

20

 

 

 

 

 

Maximum British Thermal Unit Rating ( BTU-Hr )

3033

 

3375

4403

4403

4403

4403

 

4403

 

 

 

 

 

 

 

 

 

 

 

HP 1200W Common Slot -48VDC Hot Plug Power Supply Kit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Part Number

437573-B21

 

 

 

 

 

 

 

 

Input Voltage Range ( V rms )

36-72

 

 

 

 

 

 

 

 

 

 

Frequency Range (Nominal) ( Hz )

DC

 

 

 

 

 

 

 

 

 

 

Nominal Input Voltage ( Vrms )

 

36

 

 

48

 

 

72

 

 

Maximum Rated Output Wattage Rating

 

1200

 

 

1200

 

 

1200

 

Nominal Input Current ( A rms )

 

38

 

 

28

 

 

19

 

 

Maximum Rated Input Wattage Rating ( Watts )

 

1380

 

 

1350

 

 

1365

 

Maximum Rated VA ( Volt-Amp )

 

1380

 

 

1350

 

 

1365

 

Efficiency ( % )

 

87

 

 

89

 

 

88

 

 

Power Factor

 

 

 

 

 

N/A

 

 

 

 

 

Leakage Current ( mA )

 

 

 

 

 

N/A

 

 

 

 

 

Maximum Inrush Current ( A peak )

 

20

 

 

25

 

 

35

 

 

Maximum Inrush Current duration ( mS )

 

1

 

 

1

 

 

3

 

 

Maximum British Thermal Unit Rating ( BTU-Hr )

 

4713

 

 

4610

 

 

4662

 

NOTES: To review typical system power ratings use the HP Power Advisor which is available online located at url: www.hp.com/go/proliant-energy-efficientor www.hp.com/go/hppoweradvisor

DA - 13595 Worldwide — Version 65 — March 25, 2013

Page 56

Page 56
Image 56
HP DL380 Generation 7 (G7) manual HP 1200W Common Slot Platinum Hot Plug Power Supply Kit, 220 230 240