Site Preparation

Environmental Elements

Underfloor air distribution system—Downflow air conditioning equipment located on the raised floor of the computer room uses the cavity beneath the raised floor as plenum for the supply air.

Perforated floor panels (available from the raised floor manufacturer) should be located around the perimeter of the system cabinets. Supply air emitted though the perforated floor panels is then available near the cooling air intake vents of the computer system cabinets.

Ceiling plenum air distribution system—Supply air is ducted into the ceiling plenum from upflow air conditioning equipment located in the computer room or from an air handling unit (remote).

The ceiling construction should resist air leakage. Place perforated ceiling panels (with down discharge air flow characteristics) around the perimeter of the system cabinets. The supply air emitted downward from the perforated ceiling panels is then available near the cooling air intake vents of the computer system cabinets.

Return air should be ducted back to the air conditioning equipment though the return air duct above the ceiling.

Above ceiling ducted air distribution system—Supply air is ducted into a ceiling diffuser system from upflow air conditioning equipment located in the computer room or from an air handling unit (remote).

Adjust the supply air diffuser system grilles to direct the cooling air downward around the perimeter of the computer system cabinets. The supply air is then available near the cooling air intake vents of the computer system cabinets.

Table C-1

Computer Room Environment

 

 

 

 

 

 

 

 

 

Recommended

Maximum Rate of

Non-Operating

Parameter

Operating Limits

Operating

Change (per hour)

Ranges

 

 

Range

 

 

 

 

 

 

 

 

 

Temperaturea

41° - 95° F

68° - 77° F

20° C/hour

-40° C - +70° C

 

(5° - 35° C)

(20° - 25° C)

 

 

 

 

 

 

 

Humidity

15% - 80%

40% - 55% RH

30% RH/hour

90% RH

 

with no condensation

non-condensing

non-condensing

non-condensing

 

(40% - 55% recommended)

 

 

@ 65° C (149° F)

 

 

 

 

 

a.The temperature ranges stated are at 0 to 5,000 feet. The maximum operating temperature must be de-rated by 1° C/1,000 feet from 5,000 to 10,000 feet.

Air Conditioning System Installation

All air conditioning equipment, materials, and installation must comply with any applicable construction codes. Installation of the various components of the air conditioning system must also conform to the air conditioning equipment manufacturer’s recommendations.

Humidity Level

Maintain proper humidity levels. High humidity causes galvanic actions to occur between some dissimilar metals. This eventually causes a high resistance between connections, leading to equipment failures. High humidity can also have an adverse affect on some magnetic tapes and paper media.

112

Appendix C

Page 134
Image 134
HP RP7405/7410 manual Air Conditioning System Installation, Humidity Level, Table C-1 Computer Room Environment

RP7405/7410 specifications

The HP RP7405 and RP7410 are high-performance servers in the HP Integrity line, specifically designed for mission-critical applications. These servers are built on the Itanium architecture and showcase HP's commitment to reliability, scalability, and performance. Targeted primarily at the enterprise market, both models are ideal for data-intensive workloads, virtualization, and large databases.

One of the standout features of the RP7405 and RP7410 is their robust architecture. The servers utilize HP's NonStop technology, ensuring high availability and fault tolerance. This architecture is designed to provide continuous uptime, which is crucial for businesses dependent on uninterrupted access to their data and applications. The RP7405 supports up to 4 processors, while the RP7410 can accommodate up to 8 processors, allowing for enhanced compute power and the ability to handle increasingly demanding workloads.

In terms of memory, the RP7405 and RP7410 support significant RAM configurations, making them capable of handling large memory-intensive applications. They are equipped with advanced memory management technology, including ECC (Error-Correcting Code) memory, which helps to detect and correct data corruption, thereby enhancing system reliability.

The servers employ HP's Virtual Partition (vPars) technology, which allows for efficient server consolidation by enabling multiple virtual servers to operate on a single physical machine. This capability enhances resource utilization and simplifies management, thus reducing IT costs while maximizing performance.

HP's Serviceguard clustering software is integrated into both servers, offering enhanced availability through active-active clustering and failover capabilities. This software ensures that workloads can be seamlessly transitioned between servers in the event of hardware failures or maintenance, further minimizing downtime.

Security is also a paramount consideration with the HP RP7405 and RP7410. The servers come equipped with advanced security features, including secure boot, encryption, and an array of compliance certifications, ensuring that sensitive data is protected against unauthorized access.

Additionally, the servers support a wide range of operating systems, including HP-UX, which is optimized for the Itanium architecture. This flexibility allows organizations to choose the operating environment that best suits their application needs.

In conclusion, the HP RP7405 and RP7410 are powerful servers designed for high-performance applications in enterprise environments. With their advanced architecture, extensive memory support, virtualization capabilities, and robust security features, these servers stand out as reliable solutions for organizations seeking to enhance their IT infrastructure while ensuring high availability and performance.