Ice-O-Matic ICE0250 Series Uneven Bridge Thickness, ICE Series, Troubleshooting Trees, Page C10

Models: ICE0250 Series

1 164
Download 164 pages 62.11 Kb
Page 40
Image 40
Uneven Bridge Thickness

ICE Series

Troubleshooting Trees

Uneven Bridge Thickness

Make sure

supply waterOK temperature is

below 100°F

(38°C)

NO

Check for water

NO

leaking out of Purge

 

Drain

 

 

 

Dirty or

defective Purge

Valve

Is water

running into

the bin?

Are the

Evaporator(s) flooded? See page E4 and E5

NO

Check the suction

pressure, is it high or

low? See pageE1

LOW

Make sure the

system is charged

properly, recover the charge and weigh in the correct amount

OK

Refer to page

E3 and E4 for

TXV diagnosis.

YES

YES

HIGH

Problem in

water system, see pages D1 and D2.

Serpentine coil

on back of evaporator could be separated, see page E4

Hot Gas Valve

could be

leaking, see

page E5

Page C10

Page 40
Image 40
Ice-O-Matic ICE0250 Series Uneven Bridge Thickness, ICE Series, Troubleshooting Trees, Page C10, Yes Yes High