Intel SC5000 manual Safety Guidelines

Models: SC5000

1 56
Download 56 pages 14.18 Kb
Page 7
Image 7

OVERCURRENT PROTECTION: The server is designed for an AC line voltage source with up to 20 amperes of overcurrent protection. If the power system for the equipment rack is installed on a branch circuit with more than 20 amperes of protection, you must provide supplemental protection for the server. If more than one server is installed in the rack, the power source for each server must be from a separate branch circuit. The overall current rating of a server configured with a 350 watt 1+1 power supply is under 12 amperes.

CAUTIONS

Temperature: The operating temperature of the server, when installed in an equipment rack, must not go below 5 °C (41 °F) or rise above 35 °C (95 °F). Extreme fluctuations in temperature can cause a variety of problems in your server.

Ventilation: The equipment rack must provide sufficient airflow to the front of the server to maintain proper cooling. It must also include ventilation sufficient to exhaust a maximum of 2000 Btu's per hour for the server. The rack selected and the ventilation provided must be suitable to the environment in which the server will be used.

Safety Guidelines

7

Page 7
Image 7
Intel SC5000 manual Safety Guidelines