IPSO T30, T45 Electrical Requirements for Gas and Steam Models, Refer to and Table

Models: T30 T45

1 21
Download 21 pages 17.62 Kb
Page 19
Image 19

Tumblers – T30 and T45

Electrical Requirements for Gas and Steam Models

Refer to Table 4 and Table 5.

NOTE: Minimum wire sizes are obtained from Canadian Electrical Code for 75°C Conductors and are intended for use as a guideline only.

Electrical connections should be made only by a qualified electrical contractor in accordance with all applicable local and national requirements.

For T30 Gas and Steam Models (For Total Machine):

NOTE: Electrical specifications below are subject to change without notice. Always refer to product serial plate for most current specifications of product being installed.

NOTE: Use copper conductors only.

NOTE: 3 Phase Only – Each tumbler must be connected to its own individual branch circuit breaker, not fuses, to avoid the possibility of “single phasing” and causing premature failure of the motor(s).

 

 

 

Recommended

 

Recommended

 

Terminal Block

 

 

Minimum

Serial Plate Voltage

Current

Fuse or

Breaker

Connections

Conductor Size

 

Required

(Amps)

Breaker Rating

Poles

(AWG [mm2])

 

 

 

(Amps)

 

 

 

 

 

 

 

 

120V/60 Hz/1ph

L1, Neutral,

16.0

20

1

12 (3.31)

and ground

 

 

 

 

 

 

 

 

 

208-240V/60Hz/1ph

L1, L2, Neutral,

8.0

10

2

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

100V/60Hz/1ph

L1, Neutral,

22.0

30

1

10 (5.26)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200-220V/60Hz/1ph

L1, Neutral,

11.6

15

1

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

100V/50Hz/1ph

L1, Neutral,

24.2

35

1

8 (8.37)

and ground

 

 

 

 

 

 

 

 

 

200V/50Hz/1ph

L1, Neutral,

15.0

20

1

12 (3.31)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230-240V/50Hz/1ph

L1, Neutral,

15.0

20

1

12 (3.31)

and ground

 

 

 

 

 

 

 

 

 

200-208V/60Hz/3ph

L1, L2, L3,

6.4

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

240V/60Hz/3ph

L1, L2, L3,

6.4

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200V/50Hz/3ph

L1, L2, L3,

5.8

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

230-240V/50Hz/3ph

L1, L2, L3,

7.0

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

380V/50 or 60Hz/3ph

L1, L2, L3,

3.0

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400-415V/50Hz/3ph

L1, L2, L3,

3.2

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

460-480V/60Hz/3ph

L1, L2, L3,

3.3

10*

3

14 (2.08)

and ground

 

 

 

 

 

 

 

 

 

* 3 Phase machines should not have fuses, breakers only.

 

 

 

 

 

 