Venting Requirements

Venting Requirements

Vent system must terminate to the outdoors.

Do not terminate the vent system in an attic or other enclosed area.

Do not use 4" (10.2 cm) laundry-type wall caps.

Use metal vent only. Rigid metal vent is recommended. Plastic or metal foil vent is not recommended.

The length of vent system and number of elbows should be kept to a minimum to provide efficient performance.

For the most efficient and quiet operation:

Use no more than three 90° elbows.

Make sure there is a minimum of 24" (61.0 cm) of straight vent between the elbows if more than 1 elbow is used.

Do not install 2 elbows together.

Use clamps to seal all joints in the vent system.

The vent system must have a damper. If the roof or wall cap has a damper, do not use the damper supplied with the range hood.

Use caulking to seal exterior wall or roof opening around the cap.

The size of the vent should be uniform.

Cold weather installations

An additional back draft damper should be installed to minimize backward cold air flow and a thermal break should be installed to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break.

The break should be as close as possible to where the vent system enters the heated portion of the house.

Makeup air

Local building codes may require the use of makeup air systems when using ventilation systems greater than specified CFM of air movement. The specified CFM varies from locale to locale.

Consult your HVAC professional for specific requirements in your area.

Venting Methods

Calculating Vent System Length

To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.

Vent Piece

Equivalent Length

45° elbow

2.5 ft

 

(0.8 m)

 

 

90° elbow

5.0 ft

 

(1.5 m)

The maximum equivalent vent lengths are:

10" (25.4 cm) round vents - 60 ft (18.3 m)

Example vent system

90 elbow

 

 

 

 

 

 

Wall cap

 

 

6 ft (1.8 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2ft

(0.6 m)

The following example falls within the maximum recommended vent length.

1

- 90° elbow

= 5.0 ft (1.5 m)

1

- wall cap

= 0.0 ft (0.0 m)

8 ft (2.4 m) straight

= 8.0 ft (2.4 m)

 

 

Length of system

= 13.0 ft (3.9 m)

A 10" (25.4 cm) round vent system is needed for installation (not included). The hood exhaust opening is 10" (25.4 cm) round.

NOTE: Flexible vent is not recommended. Flexible vent creates back pressure and air turbulence that greatly reduce performance.

Vent system can terminate either through the roof or wall.

Roof Venting

Wall Venting

A

B* For the most efficient and quiet operation:

B*

A

A. Roof cap

A. Wall cap

B. 10" (25.4 cm) round vent*

B. 10" (25.4 cm) round vent*

7

Page 7
Image 7
Jenn-Air LI3UNB Venting Requirements, Cold weather installations, Makeup air, Venting Methods, Example vent system