TABLE 1: PHYSICAL DATA

279815-PTG-D-0408

TABLE 1: PHYSICAL DATA

 

MODELS

 

 

 

ACP

 

 

 

024

030

036

 

042

048

060

 

 

 

EVAPORATOR

CENTRIFUGAL BLOWER (Dia. x Wd. in.)

10 x 8

10 x 8

10 x 8

 

11 x 10

11 x 10

11 x 10

BLOWER

FAN MOTOR HP

½

½

½

 

3 4

3 4

1

 

ROWS DEEP

2

2

3

 

3

3

3

EVAPORATOR

FINS PER INCH

15

15

13

 

16

16

16

COIL

FACE AREA (Sq. Ft.)

4.38

4.38

4.38

 

4.38

5.63

5.63

 

PROPELLER DIA. (in.)

22

22

22

 

22

22

22

CONDENSER

FAN MOTOR HP

¼

¼

¼

 

¼

¼

½

FAN

NOM. CFM TOTAL

1,800

1,800

1,800

 

2,400

3,000

3,000

 

ROWS DEEP

1

1

1

 

1

1

2

CONDENSER

FINS PER INCH

20

20

20

 

20

20

20

COIL

FACE AREA (Sq. Ft.)

12.9

12.9

12.9

 

12.9

16.4

16.4

CHARGE

REFRIGERANT 22 (lbs./oz.)

4/10

5/9

5/0

 

4/12

6/0

10/8

FILTER

FACE AREA (Sq. Ft.) / Qty. / Size

 

 

2.14 / 1 /

14" x 22”

 

 

COMPRESSOR

HERMETIC, QTY. = 1 (Type)

Recip.

Rotary

Scroll

 

Scroll

Scroll

Scroll

TABLE 2: RATINGS - ARI

 

Cooling1

 

Sound Rating2

 

Electric Heat

 

Electric Heat

 

 

 

 

Model ACP

Capacity

 

 

Nom. Capacity

 

Nom. Capacity

80/67-95 °F

 

(decibels)

 

KW

 

KW

 

 

 

 

 

MBH

SEER

 

 

 

(single phase)

 

(three phase)

024

24.0

13.00

 

80

 

5.0, 7.5, 10.0

 

N / A

030

29.2

13.00

 

82

 

5.0, 7.5, 10.0, 15.0

 

N / A

036

35.0

13.00

 

75

 

5.0, 7.5, 10.0, 15.0

 

10.0,

15.0

042

42.0

13.00

 

77

 

5.0, 7.5, 10.0, 15.0

 

10.0,

15.0

048

46.0

13.00

 

82

 

10.0, 15.0, 20.0, 25.0

 

10.0, 15.0,

20.0, 25.0

060

58.0

13.00

 

82

 

10.0, 15.0, 20.0, 25.0

 

10.0, 15.0,

20.0, 25.0

1.Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.

2.Rated in accordance with ARI Standard 270.

SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.