TABLE 1: PHYSICAL DATA
| MODELS |
|
|
| ACP |
|
| |
| 024 | 030 | 036 |
| 042 | 048 | 060 | |
|
|
| ||||||
EVAPORATOR | CENTRIFUGAL BLOWER (Dia. x Wd. in.) | 10 x 8 | 10 x 8 | 10 x 8 |
| 11 x 10 | 11 x 10 | 11 x 10 |
BLOWER | FAN MOTOR HP | ½ | ½ | ½ |
| 3 4 | 3 4 | 1 |
| ROWS DEEP | 2 | 2 | 3 |
| 3 | 3 | 3 |
EVAPORATOR | FINS PER INCH | 15 | 15 | 13 |
| 16 | 16 | 16 |
COIL | FACE AREA (Sq. Ft.) | 4.38 | 4.38 | 4.38 |
| 4.38 | 5.63 | 5.63 |
| PROPELLER DIA. (in.) | 22 | 22 | 22 |
| 22 | 22 | 22 |
CONDENSER | FAN MOTOR HP | ¼ | ¼ | ¼ |
| ¼ | ¼ | ½ |
FAN | NOM. CFM TOTAL | 1,800 | 1,800 | 1,800 |
| 2,400 | 3,000 | 3,000 |
| ROWS DEEP | 1 | 1 | 1 |
| 1 | 1 | 2 |
CONDENSER | FINS PER INCH | 20 | 20 | 20 |
| 20 | 20 | 20 |
COIL | FACE AREA (Sq. Ft.) | 12.9 | 12.9 | 12.9 |
| 12.9 | 16.4 | 16.4 |
CHARGE | REFRIGERANT 22 (lbs./oz.) | 4/10 | 5/9 | 5/0 |
| 4/12 | 6/0 | 10/8 |
FILTER | FACE AREA (Sq. Ft.) / Qty. / Size |
|
| 2.14 / 1 / | 14" x 22” |
|
| |
COMPRESSOR | HERMETIC, QTY. = 1 (Type) | Recip. | Rotary | Scroll |
| Scroll | Scroll | Scroll |
TABLE 2: RATINGS - ARI
| Cooling1 |
| Sound Rating2 |
| Electric Heat |
| Electric Heat | ||
|
|
|
| ||||||
Model ACP | Capacity |
|
| Nom. Capacity |
| Nom. Capacity | |||
| (decibels) |
| KW |
| KW | ||||
|
|
|
| ||||||
| MBH | SEER |
|
|
| (single phase) |
| (three phase) | |
024 | 24.0 | 13.00 |
| 80 |
| 5.0, 7.5, 10.0 |
| N / A | |
030 | 29.2 | 13.00 |
| 82 |
| 5.0, 7.5, 10.0, 15.0 |
| N / A | |
036 | 35.0 | 13.00 |
| 75 |
| 5.0, 7.5, 10.0, 15.0 |
| 10.0, | 15.0 |
042 | 42.0 | 13.00 |
| 77 |
| 5.0, 7.5, 10.0, 15.0 |
| 10.0, | 15.0 |
048 | 46.0 | 13.00 |
| 82 |
| 10.0, 15.0, 20.0, 25.0 |
| 10.0, 15.0, | 20.0, 25.0 |
060 | 58.0 | 13.00 |
| 82 |
| 10.0, 15.0, 20.0, 25.0 |
| 10.0, 15.0, | 20.0, 25.0 |
1.Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
2.Rated in accordance with ARI Standard 270.
SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric power input in
Johnson Controls Unitary Products | 5 |