TABLE 7: COOLING CAPACITIES - 4 TON (ACP048) (CONTINUED)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

47.1

5.0

23.3

19.1

14.9

-

-

-

43.8

5.5

21.7

17.7

13.7

-

-

-

 

 

72

42.2

5.0

29.5

25.3

21.1

16.9

-

-

38.8

5.5

27.7

23.7

19.7

15.7

-

-

1200

 

67

37.2

4.9

35.7

31.5

27.3

23.1

18.9

-

33.7

5.4

33.7

29.7

25.7

21.7

17.7

-

 

 

62

33.1

4.8

33.1

33.1

33.1

28.9

24.7

20.5

29.9

5.3

29.9

29.9

29.9

27.2

23.2

19.3

 

 

57

33.0

4.7

33.0

33.0

33.0

28.8

24.7

20.5

30.7

5.4

30.7

30.7

30.7

26.7

22.8

18.8

 

 

77

48.3

5.1

30.9

21.8

16.2

-

-

-

44.9

5.6

31.0

20.6

15.0

-

-

-

 

 

72

43.2

5.1

34.1

28.5

22.9

17.3

-

-

39.8

5.6

32.7

27.1

21.5

15.8

-

-

1400

 

67

38.1

5.0

37.4

35.2

29.6

24.0

18.4

-

34.6

5.5

34.5

33.6

28.0

22.3

16.7

-

 

 

62

33.9

4.9

33.9

33.9

33.9

28.3

22.7

17.1

30.6

5.4

30.6

30.6

30.6

25.8

20.0

14.4

 

 

57

33.9

4.8

33.9

33.9

33.9

28.2

22.6

17.0

31.5

5.5

31.5

31.5

31.5

26.0

20.2

14.6

 

 

77

49.5

5.2

38.4

24.5

17.4

-

-

-

46.0

5.7

40.2

23.5

16.2

-

-

-

 

 

72

44.3

5.2

38.7

31.7

24.7

17.7

-

-

40.7

5.7

37.8

30.5

23.2

15.9

-

-

1600

 

67

39.1

5.1

39.1

39.0

31.9

24.9

17.9

-

35.4

5.6

35.4

35.4

30.3

23.0

15.7

-

 

 

62

34.7

5.1

34.7

34.7

34.7

27.7

20.7

13.6

31.4

5.5

31.4

31.4

31.4

24.3

16.8

9.5

 

 

57

34.7

4.9

34.7

34.7

34.7

27.7

20.6

13.6

32.3

5.6

32.3

32.3

32.3

25.3

17.7

10.4

 

 

72

44.8

5.2

41.0

33.3

25.6

18.0

-

-

41.2

5.7

39.7

32.0

24.2

16.4

-

-

1800

 

67

39.5

5.2

39.5

39.5

33.2

25.5

17.9

-

35.9

5.7

35.9

35.9

31.5

23.7

16.0

-

 

62

35.1

5.1

35.1

35.1

35.1

27.5

19.8

12.2

31.7

5.6

31.7

31.7

31.7

24.1

16.2

8.4

 

 

 

 

57

35.1

5.0

35.1

35.1

35.1

27.4

19.8

12.1

32.7

5.6

32.7

32.7

32.7

25.1

17.1

9.4

 

 

72

45.4

5.3

43.2

34.9

26.6

18.3

-

-

41.7

5.8

41.6

33.4

25.1

16.9

-

-

2000

 

67

40.0

5.2

40.0

40.0

34.4

26.1

17.8

-

36.3

5.7

36.3

36.3

32.7

24.5

16.2

-

 

62

35.6

5.2

35.6

35.6

35.6

27.3

19.0

10.7

32.1

5.6

32.1

32.1

32.1

23.9

15.6

7.4

 

 

 

 

57

35.5

5.0

35.5

35.5

35.5

27.2

18.9

10.6

33.0

5.7

33.0

33.0

33.0

24.8

16.6

8.3

1.These capacities are Net Capacities.

2.These ratings include the compressor, condenser fan and supply air blower motors.

Johnson Controls Unitary Products