Johnson Controls ACPU024 THRU 060 manual PTG-D-0408, Johnson Controls Unitary Products

Models: ACPU024 THRU 060

1 32
Download 32 pages 17.42 Kb
Page 7
Image 7
1.These capacities are Net Capacities.

279815-PTG-D-0408

TABLE 3: COOLING CAPACITIES - 2 TON (ACP024) (CONTINUED)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

 

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

 

77

22.9

2.5

11.4

8.7

6.0

-

-

-

21.2

2.7

11.0

8.2

5.4

-

 

-

-

 

 

72

20.4

2.4

15.0

12.3

9.6

6.9

-

-

18.1

2.6

14.4

11.6

8.8

6.0

 

-

-

600

 

67

17.8

2.3

17.0

16.0

13.2

10.5

7.8

-

15.1

2.5

15.0

15.0

12.2

9.4

 

6.6

-

 

 

62

17.4

2.3

17.0

16.9

14.2

11.5

8.8

6.1

15.0

2.4

15.0

15.0

12.6

9.8

 

7.0

4.2

 

 

57

17.0

2.3

17.0

17.0

15.1

12.4

9.6

6.9

15.0

2.4

15.0

15.0

13.2

10.4

 

7.6

4.8

 

 

77

23.4

2.6

14.5

10.3

6.5

-

-

-

21.8

2.8

13.4

10.2

5.9

-

 

-

-

 

 

72

20.8

2.5

16.4

13.6

10.4

7.3

-

-

18.7

2.6

15.3

12.9

9.7

6.4

 

-

-

700

 

67

18.2

2.3

17.3

16.8

14.4

11.3

8.1

-

15.5

2.5

15.3

15.3

13.4

10.1

 

6.9

-

 

 

62

17.8

2.3

17.3

17.3

15.5

12.3

9.2

6.1

15.5

2.5

15.3

15.3

13.9

10.7

 

7.3

4.1

 

 

57

17.3

2.3

17.3

17.3

16.4

13.3

10.1

7.0

15.4

2.5

15.4

15.4

14.5

11.4

 

8.0

4.7

 

 

77

23.9

2.6

17.7

11.9

7.0

-

-

-

22.5

2.8

15.8

12.3

6.5

-

 

-

-

 

 

72

21.3

2.5

17.7

14.8

11.3

7.7

-

-

19.2

2.7

15.8

14.3

10.5

6.8

 

-

-

800

 

67

18.6

2.4

17.7

17.7

15.5

12.0

8.5

-

16.0

2.5

15.8

15.8

14.6

10.9

 

7.1

-

 

 

62

18.2

2.4

17.7

17.7

16.7

13.2

9.6

6.1

15.9

2.5

15.8

15.8

15.1

11.6

 

7.7

3.9

 

 

57

17.7

2.3

17.7

17.7

17.7

14.2

10.6

7.1

15.9

2.5

15.9

15.9

15.9

12.3

 

8.4

4.6

 

 

72

21.7

2.5

18.1

16.1

12.2

8.2

-

-

19.8

2.7

16.3

15.7

11.5

7.3

 

-

-

900

 

67

19.0

2.4

18.1

18.1

16.8

12.8

8.9

-

16.5

2.5

16.3

16.3

15.9

11.7

 

7.5

-

 

62

18.6

2.4

18.1

18.1

17.6

13.6

9.7

5.8

16.4

2.5

16.3

16.3

16.0

11.8

 

7.6

3.4

 

 

 

 

 

57

18.1

2.4

18.1

18.1

18.1

14.1

10.2

6.3

16.3

2.5

16.3

16.3

16.3

12.2

 

7.9

3.7

 

 

72

22.2

2.5

18.5

17.4

13.1

8.7

-

-

20.3

2.7

16.8

17.1

12.4

7.7

 

-

-

1000

 

67

19.4

2.4

18.5

18.5

18.0

13.7

9.3

-

16.9

2.6

16.8

16.8

16.8

12.1

 

7.9

-

 

62

19.0

2.4

18.5

18.5

18.5

14.1

9.8

5.5

16.9

2.6

16.8

16.8

16.8

12.1

 

7.5

2.8

 

 

 

 

 

57

18.5

2.4

18.5

18.5

18.5

14.1

9.8

5.5

16.8

2.5

16.8

16.8

16.8

12.1

 

7.5

2.8

1.These capacities are Net Capacities.

2.These ratings include the compressor, condenser fan and supply air blower motors.

Johnson Controls Unitary Products

7

Page 7
Image 7
Johnson Controls ACPU024 THRU 060 manual PTG-D-0408, Johnson Controls Unitary Products, These capacities are Net Capacities