TABLE 5: COOLING CAPACITIES - 3 TON (ACP036) (CONTINUED)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

36.0

3.6

17.9

14.4

10.9

-

-

-

32.6

3.9

16.6

13.2

9.9

-

-

-

 

 

72

32.6

3.5

23.2

19.7

16.2

12.8

-

-

29.5

3.8

21.7

18.4

15.1

11.7

-

-

1000

 

67

29.3

3.4

28.6

25.1

21.6

18.1

14.6

-

26.4

3.6

26.4

23.5

20.2

16.9

13.6

-

 

 

62

26.7

3.3

26.7

26.7

26.9

23.4

20.0

16.5

24.1

3.5

24.1

24.1

24.1

22.4

19.1

15.7

 

 

57

26.5

3.3

26.5

26.5

26.4

23.0

19.5

16.0

24.2

3.6

24.2

24.2

24.2

20.9

17.6

14.2

 

 

77

36.7

3.7

23.4

16.2

11.7

-

-

-

33.2

4.0

23.8

15.3

10.8

-

-

-

 

 

72

33.3

3.6

26.5

22.0

17.5

13.0

-

-

30.0

3.9

25.5

20.9

16.4

11.9

-

-

1125

 

67

29.9

3.5

29.5

27.8

23.3

18.8

14.3

-

26.8

3.7

26.8

26.6

22.1

17.5

13.0

-

 

 

62

27.2

3.4

27.2

27.2

27.4

22.9

18.4

13.9

24.5

3.6

24.5

24.5

24.5

20.9

16.3

11.8

 

 

57

27.1

3.4

27.1

27.1

27.0

22.5

18.1

13.6

24.6

3.7

24.6

24.6

24.6

20.3

15.6

11.1

 

 

77

37.4

3.8

29.0

18.1

12.6

-

-

-

33.7

4.1

31.1

17.4

11.7

-

-

-

 

 

72

34.0

3.7

29.8

24.3

18.8

13.3

-

-

30.5

4.0

29.2

23.5

17.8

12.1

-

-

1250

 

67

30.5

3.6

30.5

30.5

25.0

19.5

14.0

-

27.3

3.8

27.3

27.3

23.9

18.2

12.5

-

 

 

62

27.8

3.5

27.8

27.8

27.8

22.3

16.8

11.3

24.9

3.8

24.9

24.9

24.9

19.4

13.5

7.8

 

 

57

27.6

3.5

27.6

27.6

27.6

22.1

16.6

11.1

25.1

3.8

25.1

25.1

25.1

19.6

13.7

8.0

 

 

72

34.3

3.8

31.1

25.3

19.4

13.6

-

-

30.8

4.0

30.1

24.2

18.3

12.3

-

-

1375

 

67

30.8

3.7

30.8

30.8

25.8

20.0

14.1

-

27.6

3.9

27.6

27.6

24.5

18.5

12.6

-

 

62

28.0

3.6

28.0

28.0

28.0

22.2

16.3

10.5

25.2

3.8

25.2

25.2

25.2

19.3

13.3

7.3

 

 

 

 

57

27.9

3.6

27.9

27.9

27.9

22.0

16.2

10.3

25.3

3.8

25.3

25.3

25.3

19.5

13.4

7.5

 

 

72

34.6

3.8

32.5

26.3

20.1

13.8

-

-

31.1

4.1

31.1

24.9

18.7

12.5

-

-

1500

 

67

31.1

3.7

31.1

31.1

26.7

20.5

14.2

-

27.8

3.9

27.8

27.8

25.1

18.9

12.7

-

 

62

28.3

3.6

28.3

28.3

28.3

22.1

15.9

9.6

25.4

3.8

25.4

25.4

25.4

19.2

13.0

6.8

 

 

 

 

57

28.2

3.6

28.2

28.2

28.2

21.9

15.7

9.5

25.5

3.9

25.5

25.5

25.5

19.4

13.2

7.0

1.These capacities are Net Capacities.

2.These ratings include the compressor, condenser fan and supply air blower motors.

Johnson Controls Unitary Products