Figure 10: Unit Control Board

430645-YIM-D-0610

Table 11: PD180 thru 240 Unit Control Board Flash Codes

 

 

GREEN

RED

RED

RED

RED

FLASH CODE

DESCRIPTION

LED

LED

LED

LED

LED

 

 

16

8

4

2

1

 

 

 

 

 

 

 

On Steady

This is a Control Failure

-

-

-

-

-

1 Flash

Not Applicable

-

-

-

-

-

2 Flashes

Control waiting ASCD1

Flashing

Off

Off

On

Off

3 Flashes

HPS1 Compressor Lockout

Off

Off

Off

On

On

4 Flashes

HPS2 Compressor Lockout

Off

Off

On

Off

Off

5 Flashes

LPS1 Compressor Lockout

Off

Off

On

Off

On

6 Flashes

LPS2 Compressor Lockout

Off

Off

On

On

Off

7 Flashes

FS1 Compressor Lockout2

Off

Off

On

On

On

8 Flashes

FS2 Compressor Lockout2

Off

On

Off

Off

Off

10 Flashes

Compressors Locked Out on Low Outdoor Air Temperature1

Flashing

On

Off

On

Off

12 Flashes

Unit Locked Out due to Fan Overload Switch Failure

Off

On

On

Off

Off

13 Flashes

Compressor Held Off due to Low Voltage1

Flashing

On

On

Off

On

14 Flashes

EEPROM Storage Failure

Off

On

On

On

Off

OFF

No Power or Control Failure

Off

Off

Off

Off

Off

1.Non-alarm condition.

2.Freeze - stat not applicable.

Check

Alarm

History

Reset All

ASCDs for

One Cycle

Non Alarm

Condition Green

LED Flashing

Current Alarm

Flashed

Red LED