Table 11: PD180 thru 240 Unit Control Board Flash Codes
|
| GREEN | RED | RED | RED | RED |
FLASH CODE | DESCRIPTION | LED | LED | LED | LED | LED |
|
| 16 | 8 | 4 | 2 | 1 |
|
|
|
|
|
|
|
On Steady | This is a Control Failure | - | - | - | - | - |
1 Flash | Not Applicable | - | - | - | - | - |
2 Flashes | Control waiting ASCD1 | Flashing | Off | Off | On | Off |
3 Flashes | HPS1 Compressor Lockout | Off | Off | Off | On | On |
4 Flashes | HPS2 Compressor Lockout | Off | Off | On | Off | Off |
5 Flashes | LPS1 Compressor Lockout | Off | Off | On | Off | On |
6 Flashes | LPS2 Compressor Lockout | Off | Off | On | On | Off |
7 Flashes | FS1 Compressor Lockout2 | Off | Off | On | On | On |
8 Flashes | FS2 Compressor Lockout2 | Off | On | Off | Off | Off |
10 Flashes | Compressors Locked Out on Low Outdoor Air Temperature1 | Flashing | On | Off | On | Off |
12 Flashes | Unit Locked Out due to Fan Overload Switch Failure | Off | On | On | Off | Off |
13 Flashes | Compressor Held Off due to Low Voltage1 | Flashing | On | On | Off | On |
14 Flashes | EEPROM Storage Failure | Off | On | On | On | Off |
OFF | No Power or Control Failure | Off | Off | Off | Off | Off |
1.
2.Freeze - stat not applicable.
Check
Alarm
History
Reset All
ASCDs for
One Cycle
Non Alarm
Condition Green
LED Flashing
Current Alarm
Flashed
Red LED
Figure 10: Unit Control Board