Johnson Controls PC090 THRU 240, PD 180 THRU 240 dimensions Electrical Data

Models: PC090 THRU 240 PD 180 THRU 240

1 33
Download 33 pages 57.96 Kb
Page 9
Image 9
Electrical Data

430645-YIM-D-0610

Electrical Data

Table 5:

Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

 

Compressors

 

 

Outdoor Fan Motor

 

Pwr Conv Outlet

Minimum

Maximum

 

Power

Qty

RLA

MCC

LRA

Power

HP

Qty

FLA

FLA

Circuit

Fuse Size

 

 

Supply

(each)

(each)

(each)

Supply

(each)

Ampacity1

(A)2

 

 

208/230-3-60

1

25.0

39

164

208/230-1-60

1/3

2

2.1

-

35.5

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PC090

 

460-3-60

1

12.2

19

100

460-1-60

1/3

2

1.2

-

17.6

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

1

9.0

14

78

575-1-60

1/3

2

0.9

-

13.1

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

18.1

28.3

137

208/230-1-60

3/4

2

3.0

-

46.8

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PC120

 

460-3-60

2

9.0

14.0

62

460-1-60

3/4

2

1.6

-

23.5

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

6.8

10.6

50

575-1-60

3/4

2

1.4

-

18.0

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

-

64.7

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PC180

 

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

-

32.2

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

-

24.0

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

-

64.7

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PD180

 

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

-

32.2

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

-

24.0

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

-

79.8

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PC240

 

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

-

44.0

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

-

32.9

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

-

79.8

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PD240

 

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

-

44.0

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

-

32.9

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.

2.Maximum fuse or maximum circuit breaker (HACR type per NEC).

Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Table 6:

Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressors

 

 

Outdoor Fan Motor

 

 

Pwr Conv Outlet

Minimum

Maximum

Model

 

Power

Qty

RLA

MCC

LRA

Power

HP

Qty

FLA

 

FLA

Circuit

Fuse Size

 

 

Supply

(each)

(each)

(each)

Supply

(each)

 

Ampacity1

(A)2

 

 

208/230-3-60

1

25.0

39

164

208/230-1-60

1/3

2

2.1

 

10.0

45.5

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PC090

 

460-3-60

1

12.2

19

100

460-1-60

1/3

2

1.2

 

5.0

22.6

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

1

9.0

14

78

575-1-60

1/3

2

0.9

 

4.0

17.1

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

18.1

28.3

137

208/230-1-60

3/4

2

3.0

 

10.0

56.8

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PC120

 

460-3-60

2

9.0

14.0

62

460-1-60

3/4

2

1.6

 

5.0

28.5

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

6.8

10.6

50

575-1-60

3/4

2

1.4

 

4.0

22.0

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

 

10.0

74.7

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PC180

 

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

 

5.0

37.2

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

 

4.0

28.0

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

25.0

39

164

208/230-1-60

1/3

4

2.1

 

10.0

74.7

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PD180

 

460-3-60

2

12.2

19

100

460-1-60

1/3

4

1.2

 

5.0

37.2

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

9.0

14

78

575-1-60

1/3

4

0.9

 

4.0

28.0

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

 

10.0

89.8

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PC240

 

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

 

5.0

49.0

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

 

4.0

36.9

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

30.1

47

225

208/230-1-60

3/4

4

3.0

 

10.0

89.8

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PD240

 

460-3-60

2

16.7

26

114

460-1-60

3/4

4

1.6

 

5.0

49.0

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

12.2

19

80

575-1-60

3/4

4

1.4

 

4.0

36.9

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.

2.Maximum fuse or maximum circuit breaker (HACR type per NEC).

Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Johnson Controls Unitary Products

9

Page 9
Image 9
Johnson Controls PC090 THRU 240, PD 180 THRU 240 dimensions Electrical Data