Johnson Controls PD 180 THRU 240 Physical Data, All Compressors include crankcase heater

Models: PC090 THRU 240 PD 180 THRU 240

1 33
Download 33 pages 57.96 Kb
Page 4
Image 4
Physical Data

430645-YIM-D-0610

Physical Data

Table 1: PC090 - 240 and PD180 - 240 Physical Data

Component

 

 

 

Models

 

 

 

PC090

PC120

PC180

PD180

PC240

PD240

 

 

Nominal Tonnage

 

7.5

10

15

15

20

20

REFRIGERANT

 

 

 

 

 

 

 

Refrigerant type

 

R-410A

R-410A

R-410A

R-410A

R-410A

R-410A

Holding charge (lb)1

 

1.0

1.0

1.0

1.0

1.0

1.0

Operating Charge (lb)2

System #1

23.9

27.5

54.0

27.0

60.0

34.0

System #2

---

---

---

27.0

---

34.0

 

DIMENSIONS (inches)

 

 

 

 

 

 

 

Length

 

59.1

59.1

59.1

59.1

59.1

59.1

Width

 

31.9

31.9

64.1

64.1

64.1

64.1

Height

 

44.5

50.0

44.5

44.5

50.0

50.0

WEIGHTS (lb)

 

 

 

 

 

 

 

Shipping

 

421

543

947

921

1116

1090

Operating

 

430

574

968

942

1152

1126

COMPRESSORS3

 

 

 

 

 

 

 

Type

 

Single Scroll

Tandem Scroll

Tandem Scroll

Single Scroll

Tandem Scroll

Single Scroll

Quantity

 

1

1

1

2

1

2

Cooling

 

 

 

 

 

 

 

Nominal Capacity (Tons)

System #1

7.5

10

15

7.5

20

10

System #2

---

---

---

7.5

---

10

 

Capacity Stages

System #1

1

2

2

1

2

1

System #2

---

---

---

1

---

1

 

Heating

 

 

 

 

 

 

 

Nominal Capacity (Tons)

System #1 & #2

7.5

10

15

15

20

20

Capacity Stages

System #1 & #2

1

1

1

1

1

1

SYSTEM DATA

 

 

 

 

 

 

 

No. Refrigeration Circuits

 

1

1

1

2

1

2

Suction Line OD (in.)

 

1 1/8

1 3/8

1 5/8

1 3/8

1 5/8

1 3/8

Liquid Line OD (in.)

 

5/8

7/8

7/8

5/8

7/8

7/8

OUTDOOR COIL DATA

 

 

 

 

 

 

 

Face area (Sq. Ft.)

 

23.8

29.0

47.5

47.5

58.1

58.1

Rows

 

2

2

2

2

2

2

Fins per inch

 

20

20

20

20

20

20

Tube diameter (in./MM)

 

0.38 / 10

0.38 / 10

0.38 / 10

0.38 / 10

0.38 / 10

0.38 / 10

Circuitry Type

 

Interlaced

Interlaced

Interlaced

Interlaced

Interlaced

Interlaced

Refrigerant Control

 

TXV

TXV

TXV

TXV

TXV

TXV

CONDENSER FAN DATA

 

 

 

 

 

 

 

No. Fans / Diameter (in.)

 

2/24

2/24

4/24

4/24

4/24

4/24

Type

 

Axial

Axial

Axial

Axial

Axial

Axial

Drive type

 

Direct

Direct

Direct

Direct

Direct

Direct

No. speeds

 

1

1

1

1

1

1

Number of motors

System #1

2

2

4

2

4

2

System #2

---

---

---

2

---

2

 

Motor HP (ea.)

 

1/3

3/4

1/3

1/3

3/4

3/4

Rotation4

 

CW

CW

CW

CW

CW

CW

RPM

 

850

1100

850

850

1100

1100

Nominal CFM

System #1

7500

9800

15000

7500

19600

9800

System #2

---

---

---

7500

---

9800

 

1.Holding Charge is the amount in the unit as shipped from the factory.

2.Includes matched evaporator unit with 25 ft of piping.

3.All Compressors include crankcase heater.

4.When viewing the shaft end of the motor.

4

Johnson Controls Unitary Products

Page 4
Image 4
Johnson Controls PD 180 THRU 240, PC090 THRU 240 dimensions Physical Data, All Compressors include crankcase heater