Discharge Pressure (psi)
|
|
|
|
| Cooling Charging Curves |
|
|
|
|
|
| |||||
|
|
|
|
|
|
| PC180 |
|
|
|
|
|
|
|
| |
600 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (F) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
500 |
|
|
|
|
|
|
|
|
|
|
|
| 115° |
|
| Condenser |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| 105° |
|
| Entering |
400 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| 95° |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| 85° |
|
| Air |
300 |
|
|
|
|
|
|
|
|
|
|
|
| 75° |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Outdoor | ||
|
|
|
|
|
|
|
|
|
|
|
|
| 65° |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
200 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
120 | 130 | 140 | 150 | 160 | 170 |
| 180 |
Suction Pressure (psi)
1.Make sure that all condenser fans are running when charging.
2.This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been adjusted in the field, the charging chart may no longer apply.
Figure 13: PC180 Charging Chart
Cooling Charging Curves
PD180
Discharge Pressure (psi)
600 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| (F) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
500 |
|
|
|
|
|
|
|
|
|
|
|
| 115° |
| Condenser |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| 105° |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
400 |
|
|
|
|
|
|
|
|
|
|
|
| 95° |
| EnteringAir |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| 85° |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
300 |
|
|
|
|
|
|
|
|
|
|
|
| 75° |
| Outdoor |
|
|
|
|
|
|
|
|
|
|
|
| 65° |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
200 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
120 | 130 | 140 | 150 | 160 | 170 |
| 180 |
Suction Pressure (psi)
1.Make sure that all condenser fans are running when charging.
2.This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been adjusted in the field, the charging chart may no longer apply.
Figure 14: PD180 Charging Chart
28 | Johnson Controls Unitary Products |