Johnson Controls TM9T*MP Section V Electrical Power, GAS Orifice Conversion for Propane LP

Models: TM9T*MP

1 38
Download 38 pages 56.78 Kb
Page 11
Image 11

505309-UIM-D-0511

GAS ORIFICE CONVERSION FOR PROPANE (LP)

This furnace is constructed at the factory for natural gas-fired operation, but may be converted to operate on propane (LP) gas by using a factory-supplied LP conversion kit. Follow the instructions supplied with the LP kit.

HIGH ALTITUDE GAS ORIFICE CONVERSION

This furnace is constructed at the factory for natural gas-fired operation at 0 –7,999 feet (0 – 2,438 m) above sea level.

Table 5: Nominal Manifold Pressure - High Fire

 

 

Manifold Pressures (in. w.c.)

 

 

 

 

 

Altitude (feet)

 

 

 

 

0-7999

8000-8999

9000-9999

 

 

800

3.5

3.5

3.5

ValueHeatingGas

ft.)(BTU/cu

850

3.5

3.5

3.5

1100

3.2

2.7

2.4

 

 

900

3.5

3.5

3.5

 

 

950

3.5

3.5

3.3

 

 

1000

3.5

3.2

2.9

 

 

1050

3.5

2.9

2.7

 

 

 

 

 

 

 

 

2500 (LP)

9.8

8.2

7.5

TABLE 6: Nominal Manifold Pressure - Low Fire

 

 

 

 

 

 

 

First Stage Manifold Pressures (in. w.c.)

 

 

 

 

 

 

 

 

 

 

 

Altitude (feet)

 

 

 

 

0-7999

8000-8999

9000-9999

 

 

800

1.7

1.7

1.7

ValueHeatingGas

ft.)(BTU/cu

850

1.7

1.7

1.7

1100

1.3

1.2

1.1

 

 

900

1.7

1.7

1.7

 

 

950

1.7

1.7

1.5

 

 

1000

1.6

1.5

1.4

 

 

1050

1.5

1.4

1.3

 

 

 

 

 

 

 

 

2500 (LP)

4.1

3.8

3.5

The manifold pressure must be changed in order to maintain proper and safe operation when the furnace is installed in a location where the altitude is greater than 7,999 feet (2,438 m) above sea level. Refer to Table 5 for proper manifold pressure settings.

HIGH ALTITUDE PRESSURE SWITCH CONVERSION

For installation where the altitude is less than 5,000 feet (1,524m), it is not required that the pressure switch be changed unless you are in an area subject to low pressure inversions.

Manifold Pressures (kPa)

 

 

 

 

Altitude (m)

 

 

 

 

0-2437

2438-2742

2743-3048

 

 

29.8

0.87

0.87

0.87

HeatingValue

 

31.7

0.87

0.87

0.87

(MJ/cum)

33.5

0.87

0.87

0.87

35.4

0.87

0.87

0.81

 

 

37.3

0.87

0.80

0.73

Gas

 

39.1

0.87

0.73

0.67

 

41.0

0.80

0.66

0.61

 

 

93.2 (LP)

2.44

2.03

1.86

 

 

 

 

 

 

First Stage Manifold Pressures (kPa)

 

 

 

 

 

 

 

 

 

 

 

Altitude (m)

 

 

 

 

0-2437

2438-2742

2743-3048

 

 

29.8

0.42

0.42

0.42

HeatingValue

 

31.7

0.42

0.42

0.42

(MJ/cum)

33.5

0.42

0.42

0.42

35.4

0.42

0.42

0.38

 

 

37.3

0.41

0.37

0.34

Gas

 

39.1

0.37

0.34

0.31

 

41.0

0.34

0.31

0.28

 

 

93.2 (LP)

1.03

0.95

0.87

DANGER

PROPANE AND HIGH ALTITUDE CONVERSION KITS

It is very important to choose the correct kit and/or gas orifices for the altitude and the type of gas for which the furnace is being installed.

Only use natural gas in furnaces designed for natural gas. Only use propane (LP) gas for furnaces that have been properly converted to use pro- pane (LP) gas. Do not use this furnace with butane gas.

Incorrect gas orifices or a furnace that has been improperly converted will create an extremely dangerous condition resulting in premature heat exchanger failure, excessive sooting, high levels of carbon monoxide, personal injury, property damage, a fire hazard and/or death.

High altitude and propane (LP) conversions are required in order for the appliance to satisfactory meet the application. An authorized distributor or dealer must make all gas conversions.

In Canada, a certified conversion station or other qualified agency, using factory specified and/or approved parts, must perform the conversion. The installer must take every precaution to insure that the furnace has been converted to the proper gas orifice size when the furnace is installed. Do not attempt to drill out any orifices to obtain the proper orifice size. Drilling out a gas orifice will cause misalignment of the burner flames, caus- ing premature heat exchanger burnout, high levels of carbon monoxide, excessive sooting, a fire hazard, personal injury, property damage and/or death.

SECTION V: ELECTRICAL POWER

ELECTRICAL POWER CONNECTIONS

Field wiring to the unit must be grounded. Electric wires that are field installed shall conform to the temperature limitation for 63°F (35°C) rise wire when installed in accordance with instructions. Refer to Table 7 in these instructions for specific furnace electrical data.

Use copper conductors only.

Johnson Controls Unitary Products

11

Page 11
Image 11
Johnson Controls TM9T*MP Section V Electrical Power, GAS Orifice Conversion for Propane LP, Electrical Power Connections

TM9T*MP specifications

Johnson Controls TM9T*MP is a state-of-the-art HVAC unit designed for modern commercial and residential applications. With its innovative technology and robust features, the TM9T*MP offers exceptional performance, efficiency, and reliability. This unit is engineered to provide optimal climate control, ensuring that indoor environments remain comfortable regardless of external weather conditions.

One of the main features of the TM9T*MP is its variable-speed compressor, which allows for precise temperature regulation and energy-efficient operation. This technology enables the unit to adjust its output based on the current demand, significantly reducing energy consumption compared to traditional systems. By operating at lower speeds during mild weather, the TM9T*MP minimizes energy costs while maintaining user comfort.

Another significant aspect of the TM9T*MP is its advanced multi-stage filtration system. This system includes a high-efficiency air filter capable of capturing a wide range of airborne particles, including dust, pollen, and allergens. This feature not only improves indoor air quality but also helps to promote a healthier living environment for occupants. Furthermore, the TM9T*MP is compatible with smart home technology, allowing users to monitor and control their HVAC system remotely through mobile devices or voice-controlled assistants.

The TM9T*MP also boasts a compact design, making it versatile for various installation environments. Its sleek profile allows for easy integration into existing spaces without requiring extensive modifications. Durability is another hallmark of this unit, as it is built with high-quality materials designed to withstand the rigors of daily use while providing long-lasting performance.

Additionally, the TM9T*MP incorporates advanced diagnostics and troubleshooting capabilities. This feature simplifies maintenance by alerting technicians to potential issues before they escalate, ensuring smooth operation and reducing downtime. Moreover, with a user-friendly interface, occupants can easily adjust settings, access energy usage data, and schedule maintenance reminders for peak performance.

In summary, Johnson Controls TM9T*MP sets a new standard in HVAC technology with its variable-speed compressor, multi-stage filtration, compact design, and smart capabilities. Committed to energy efficiency and indoor air quality, it promises to deliver comfort and sustainability in every setting.