In Canada, refer to CAN/CSA-B365, Installation Code for Solid-Fuel Burning Appliances and Equipment, also for acceptable materials, proper sizing and construction guidelines.

Stove Mounted Heatshield: A stove rear heatshield has been specifically designed for the OSLO F500.

In the U.S. and Canada the rear heatshield part number is # 154332.

NO OTHER HEAT SHIELD MAY BE USED.

NOTICE

Accessories for woodstoves for clearance reduction have been developed by many manufacturers. If not following the methods of the installation codes, be sure that any accessory you choose has been tested by an independent laboratory and carries the laboratory’s testing mark. Make sure to follow all of the manufacturer’s instructions.

Always contact your local building inspector or fire officials about restriction and requirements in your area. Reminder, it is the local officials who have final authority

MOBILE HOME INSTALLATIONS

The OSLO F500 has been approved for use in mobile homes in the U.S. and Canada, provided:

1.The stove is secured to the floor or the mobile home. Floor mounting kit #750304

2.The stove is provided outside air for combustion.

Outside Air kit #154335(see page 16 for more details)

3.The stove must be grounded to the mobile home frame per NFPA 70.

As always consult with your local building inspector or fire officials about restrictions and requirements in your area, prior to installing the stove.

UNPROTECTED ALCOVE INSTALLATION*

*USE OF THE LEFT SIDE LOAD DOOR IS PROHIBITED IN ALCOVE INSTALLATIONS.

in the installations approval.

ALCOVE

The OSLO F500 can be installed in an ALCOVE situation provided: See figures 9 and 10.

1.

The stove must be installed with listed double

 

wall pipe.

2.

In a PROTECTED alcove installation both side

 

walls and rear wall must be protected per NFPA

 

211 or CAN/CSA-B365. The wall protection

 

must be elevated 1” from the floor and at least 1”

14”

355mm

18”

460mm

14”

355mm

max. depth 48” (1220mm)

56.5” min. (1435mm)

FIGURE 9

 

off the combustible wall to allow for an air-flow.

3.

The height of the wall protection including the

 

bottom air space must be 48”.

4.

The Bottom heatshield is required in all Alcove

PROTECTED ALCOVE INSTALLATION*

*USE OF THE LEFT SIDE LOAD DOOR IS PROHIBITED IN ALCOVE INSTALLATIONS.

installations.

5. If a listed (UL/ULC) hearth board is NOT used

the hearth that is constructed MUST have a

minimum R value of 1.6 (see Appendix A).

6. Minimum ceiling height in an unprotected installa

tion, off the top of the stove is 41”(1040mm) The

minimum ceiling height off the top of the stove in

a protected ceiling installation is 15”(380mm).

7. ALCOVE floor protection must be: a UL/ULC

or WHI listed hearth pad or a non combustible

material with a minimum R value of 0.5.

6”

150mm

12”

300mm

6”

150mm

max. depth 48” (1220mm)

FIGURE 10

40.5” min. 1015mm

PROTECTION

AND AIR

SPACE MUST

COMPLY

WITH NFPA

211OR

CAN/CSA-B365.

10

Page 10
Image 10
Jotul F 500 operating instructions Mobile Home Installations, Alcove