Hearth-mount into a Masonry Fireplace

The OSLO F500 may be installed into a masonry fireplace provided the height of the opening is a minimum of 29”. The short leg package reduces the stove’s height by 2 1/4”.

When installing the OSLO F500 into a masonry fireplace, code requires that the fireplace damper plate be removed or securely fixed in the open position. A connector pipe must then extend from the stove’s flue exit through the damper area of the fireplace and into the chimney tile liner. See figure 5

The inside area of the flue liner must not be less than the area of the stove’s flue exit, and cannot be more than three times greater than the cross sectional area of the stove’s flue exit.

If the chimney liner is too large to accommodate the stove, an approved relining system must be installed to resize the flue.

A new sheet metal damper block-off plate must be installed around the connector pipe at the damper frame and sealed with the proper sealant (usually High-Temp Silicone).

Fireplace installation must also observe the proper clearances to surrounding trim and mantels (addressed in clearance section of this manual). In addition, fireplace installations must also adhere to the floor protection guidelines specified in the following section.

FIGURE6

Prefabricated Chimneys

When installing the OSLO F500 to a prefabricated metal chimney always follow the pipe manufacture’s instructions and be sure to use the components that are required. This usually includes some type of “smoke pipe adapter” that is secured to the bottom section of the metal chimney and allows the chimney pipe to be secured to it with three sheet metal screws.

See figures 6 and 7

CONNECTOR EXTENDS

TO FIRST FLUE TILE

DAMPER OPENING IS

SEALED WITH SHEETMETAL

PLATE AND SEALANT

FIGURE5

FIGURE7