3.5.1. Examples of reading or changing the PROFIdrive parameter
3.5.1.1. Example 1. Reading the PNU 964 (ID number)
AK = 1 (Request parameter value)
SPM = 0
PNU = 964 (0x03C4)
PKE
0 0 0 1 0 0 1 1 1 1 0 0 0 1 0 0
1 3 C 4
Requirement
PKW PZD
PKE IND PWE
13 C4 00 00 00 00 00 00 ・・・ ・・・
Response (Value: 0x093C)
13 C4 00 00 00 00 09 3C ・・・ ・・・
3.5.1.2. Example 2. Reading the PNU 947, IND (Fault history)
AK = 6 (Request parameter value (array))
SPM = 0
PNU = 947 (0x03B3)
IND = 0x0001 (Active fault)
PKE
0 1 1 0 0 0 1 1 1 0 1 1 0 0 1 1
6 3 B 3
Requirement
PKW PZD
PKE IND PWE
63 B3 00 01 00 00 00 00 ・・・ ・・・
Response (Value: 0x000D = Inverter over load*)
43 B3 00 01 00 00 00 0D ・・・ ・・・
* Refer to page 26 about the fault code.