E6581343 - 14 - PNU (the parameter number)
PNU R/W data type Note
915 R/W Array [10]
Unsigned16
PNU 915, IND 1 = the inverter parameter f831
PNU 915, IND 2 = the inverter parameter f832
PNU 915, IND 3 = the inverter parameter f833
PNU 915, IND 4 = the inverter parameter f834
PNU 915, IND 5 = the inverter parameter f835
PNU 915, IND 6 = the inverter parameter f836
916 R/W Array [10]
Unsigned16
PNU 916, IND 1 = the inverter parameter f841
PNU 916, IND 2 = the inverter parameter f842
PNU 916, IND 3 = the inverter parameter f843
PNU 916, IND 4 = the inverter parameter f844
PNU 916, IND 5 = the inverter parameter f845
PNU 916, IND 6 = the inverter parameter f846
918 R Unsigned16 Station address monitor (same as the inverter parameter f853).
927 R/W Unsigned16 Operator control rights (parameter identification, PKW).
Value: Mode
0: Parameters cannot be written, only read
(927 can be written).
1: Parameters can be written and read (default).
928 R/W Unsigned16 Control rights (process data, PZD).
Value: Mode
0: PZD part is disabled.
i.e. Receipt of new PZD data is ignored.
1: PZD part is enabled (default).
929 R Unsigned16 Selected PPO-type (same as the inverter parameter f830)
Value: PPO TYPE
1: PPO TYPE 1
2: PPO TYPE 2
3: PPO TYPE 3
4: PPO TYPE 4
939 R/W Unsigned16 OUT1 output terminal selection (same as f130).
Monitor is enabled using Status word bit 11.
940 R/W Unsigned16 OUT2 output terminal selectionsame as f131).
Monitor is enabled using Status word bit 12.
941 R/W Unsigned16 FL output terminal selection (same as f132).
Monitor is enabled using Status word bit 13.
942 R/W Unsigned16 OUT3 output terminal selection (same as f133).
Monitor is enabled using Status word bit 14.
943 R/W Unsigned16 OUT4 output terminal selection (same as f134).
Monitor is enabled using Status word bit 15.
947 R Array [64]
Unsigned16
Fault number
PNU 947, IND 1 = fc90 (Active fault)
PNU 947, IND 9 = fe10 (Last ackn. fault)
PNU 947, IND 17 = fe11 (Second last ackn. fault)
PNU 947, IND 25 = fe12 (Third last ackn. fault)
PNU 947, IND 33 = fe13 (Fourth last ackn. fault)
963 R Unsigned16 Detected baud rate (same as f854):
0 = 12 Mbit/s
1 = 6 Mbit/s
2 = 3 Mbit/s
3 = 1.5 Mbit/s
4 = 500 kbit/s
5 = 187.5 kbit/s
6 = 93.75 kbit/s
7 = 45.45 kbit/s
8 = 19.2 kbit/s
9 = 9.6 kbit/s
255 = Invalid baud rate
964 R Unsigned16 Identification number of the PDP002Z (0x093C)
965 R Octet String2 Profile number of the PDP002Z (0x0302)
967 R Unsigned16 Control word
968 R Unsigned16 Status word