- 9 -
3.2. STW Control Word Data
PDP002Z supports only speed control mode.
Bit Value Name Note
1 ON Drive can be started if all other start conditions are fulfilled.
0
0 OFF 1 Normal stop.
1 Operating condition Drive can be started if all other start conditions are fulfilled.
1
0 OFF 2 Coast stop.
1 Operating condition Drive can be started if all other start conditions are fulfilled.
2
0 OFF 3 Emergency Stop.
1 Operation Drive can be started if all other start conditions are fulfilled.
3
0 Inhibit operation Normal stop.
1 Operation condition No function.
4
0 Inhibit ramp-function No function.
1 Enable ramp-function No function.
5
0 Stop ramp-function No function.
1 Enable setpoint Drive can be started if all other start conditions are fulfilled.
6
0 inhibit setpoint Reference frequency is set to zero.
1 Acknowledge Fault reset (0 -> 1)
7
0 No meaning No function.
1 Inching 1 ON Inverter drives with jogging speed.
8
0 Inching 1 OF F Jogging stop, if "inching 1" was previously ON. Stop drive
accordin
g
to inverter settin
g
p
arameter.
1 Inching 2 ON No function.
9
0 Inching 2 OF F No function.
1 Control from
the automation unit
The control word and frequency setpoint (from Profibus) are
activated.
10
0 No control The control word and frequency setpoint (from Profibus) are
not valid.
11
-
15
---- Device-specification (Reserved.)