E6581343
- 20 -
4.1. How to use
The purposes are adjustment by real time command transmission, and the monitor of an
operation state by using cyclic communication of PROFIBUS.
Example 1: Command transmitting
When you want to set "0xC400" to parameter fa06, set “1 (FA06)” to parameter
f831.
And Since 0 and 1 byte of the PZD1 supports the parameter f831, if "0xC400" is set
up here, "0xC400" will be set as fa06.
Example 2: State monitoring
When you want to monitor the output current, set “3 (FD03)” to parameter f841.
The value of the parameter fd03 specified as 0 and1 byte of the PZD1 with the
parameter f841 is inputted.
VF-AS1/PS1 PDP002Z
"C400" is set as parameter fa06
PZD1 PZD2 PZD3
C4 00 ... ... ... ...
PROFIBUS Master
Parameter Value
f831 1 (FA06)
f832 ...
f833 ...
... ...
Parameter Value
f841 3 (FD03)
f842 ...
f843 ...
...
The value of a parameter fd03 is outputted.
VF-AS1/PS1 PDP002Z
PZD1 PZD2 PZD3
xx xx ... ... ... ...
PROFIBUS Master