3.5.The Access to the PROFIBUS parameter

In the cyclic PROFIBUS-DP communication, the parameter data is transferred via PPO TYPE1 and 2. If the requirement is not executed, the cause is distinguished by octet 7 and 8.

 

PKW

 

 

 

 

PZD

 

(Parameter ID/value)

 

Process data (cyclically)

 

 

 

 

 

PZD1

 

PZD2

PKE

IND

 

PWE

 

STW

 

HSW

 

 

 

 

 

ZSW

 

HIW

Octet 1 Octet 2

Octet 3 Octet 4 Octet 5

Octet 6 Octet 7

Octet 8

 

 

 

PKE (Parameter ID)

15 14 13 12

11

10

9

8

7

6

5

4

3

2

1

0

AK

SPM

PNU

(Task ID/Response ID)

 

(Parameter number)

AK (Request from Master to PDP002Z

Request ID

Function

Note

0

No task

 

1

Request parameter value

for PNU access

2

Change parameter value (word)

for PNU access

6

Request parameter value (array)

for PNU access, VF-AS1/PS1 parameter access

7

Change parameter value (array)

for PNU access, VF-AS1/PS1 parameter access

AK (Response from PDP002Z to Master)

Response ID

Function

0No response

1Transfer parameter value (word)

4

Transfer parameter value (array)

7Task can not be executed, followed by error number 0 = Illegal parameter number

1 = Parameter value cannot be changed

2 = Lower or upper limit violated

3 = Erroneous sub index

11 = No parameter change rights

17 = Task cannot be executed due to operating status (e.g. parameter is currently read-only)

18 = Other error

102 = Request not supported

SPM: always 0.

- 13 -

Page 14
Image 14
Toshiba manual Access to the Profibus parameter, AK Request from Master to PDP002Z), AK Response from PDP002Z to Master