Jotul GF100 DV manual Wall Shield Installation, Corner Installation, Standard HORIZONTAL TERM. CAP

Models: GF100 DV

1 28
Download 28 pages 56.27 Kb
Page 11
Image 11
CORNER INSTALLATION

Figure 11.

CORNER INSTALLATION

45° Elbow

Standard

HORIZONTAL

TERM. CAP

Max. Horizontal Run into a STANDARD HORIZONTAL CAP : 45° elbow + 9” + 6” sections (totalling 17” horizontal).

12” Maximum horizontal when installing the stove with a 1 ft. verticalthe stove.directly2off the rear of

12” MINIMUM vertical rise when installing a 90° elbow directly off Standard the rear of the stove

Termination

Centerline off 1 ft. rise and two 90° elbows

= 38 1/4”

(97.55 cm)

WALL THIMBLE required in all installations passing through combustible

wall.

Figure 12. A vertical run in a horizontally-terminated installation must rise a minimum of 1 ft. The horizontal run must be a minimum of 1 ft.

Wall Shield Installation

The decorative Wall Shield, included with the Nordic QT, is used to cover the vent hole in the wall in installations vented directly off the rear of the stove. Follow this procedure:

1.Remove the top two 1/4” hex head screws from the rear shroud of the stove.

2.Align the holes in the wall shield with the holes in the rear shroud.

3.Secure the wall shield to the stove with the two 1/4” hex head screws. See fig. 13.

Figure 13.

Wall Shield installation.

 

21/2

12 ”

64mm

3053”

mm 76mm

Figure 14. Termination

Clearance to overhangs

11

Page 11
Image 11
Jotul GF100 DV Wall Shield Installation, Corner Installation, Standard HORIZONTAL TERM. CAP, Wall Shield installation