Kenmore 153.327563 Troubleshooting Guide, Start Up Conditions, Thermal Expansion, Expansion Tank

Models: 153.327864 153.327863 153.327363 153.327564 153.327364 153.327464 153.327264 153.327664 153.327164 153.327663 153.327463 153.327563

1 28
Download 28 pages 22.48 Kb
Page 21
Image 21
Troubleshooting Guide

Troubleshooting Guide

Start Up Conditions

THERMAL EXPANSION

Water supply systems may, because of such events as high line pressure, frequent cut-offs, the effects of water hammer among others, have installed devices such as pressure reducing valves, check valves, back flow preventers, etc._to control these types of _roblems. When these devices are not equipped with an internal

y-pass, and no other measures are taken, the devices cause the water system to be closed. As water is heated, it expands (ther-

mal expansion) and closed systems do not allow for the expan- sion of heated water.

The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving point of the water heater's temperature-pressure relief valve is reached, the valve will relieve the excess pressure. The temperature-pressure relief valve is not intended for the constant relief of thermal

expansion. This is an unacceptable condition and must be cor- rected.

It is recommended that any devices installed which could create a closed system have a by-pass and/or the system have an expan- sion tank to relieve the pressure built by thermal expansion.

Thermal expansion tanks are available from Sears stores and

through the Sears Service Centers. Contact the local plumbing inspector, water supplier and/or the Sears Service Center for assistance in controlling these situations.

HOT

COLD WATERHEATER

(3)

 

COLDWATER

PRESSURE

 

,INLETFITTING

REDUCING

 

 

VALVEWITH

 

 

BY-PASS

 

EXPANSION

 

 

TANK

1

 

O)

 

(2)

 

PRESSUREGAUGE

WATER

SHUTOFF

RECOMMENDED INSTALLATION

(VERTICAL MOUNTING)

 

WATER HEATER

FLOOR,CEILING

 

COLD WATER

jols_, ETC.

 

INLET FITTING

 

HOT

COLD

STRAPPING

 

 

Thermal Expansion Tank Specifications

Model

Tank

Capacity

Dimensions

in

Inches

Pipe

Fitting

Number

In

Gallons

Diameter

Length

On

Tank

153.331020

 

2

8 inches

12_

inches

_"

Male

153.331050

 

5

11 inches

14_

inches

3/,,, Male

Expansion Tank

Sizing

Chart

 

 

 

 

Inlet*

Water

Heater

Capacity

(Gallons)

 

 

Water

 

 

 

 

 

 

Expansion

Pressure

30

 

40

50

66

82

40psi

2

i

2

2

5

5

Tank

Capacity

50psi

2

 

_

2

5

5

Needed

60psi

2_--_

 

 

5

5

5

 

70psi

 

2 _

5

 

2

 

5

5

 

80psi

21

7T5

5

5

*Highest recorded inlet water pressure in a 24 hour period or regulated water pressure.

NOTE: Expansion tanks are pre-charged with a 40 psi air

charge. If the i,nlet water pressure is higher than 40 psi, the

expansion tanks air pressure must be adjusted to match that pressure, but must not be higher than 80 psi.

o)

PRESSURE

REDUCING INLET COLD

VALVEWITH WATER

O)B'_PASS SHUTOFF

EXPANSION

(2)

PRESSUREGAUGE

ALTERNATE RECOMMENDED

INSTALLATION

(HORIZONTAL MOUNTING)

STRANGE SOUNDS

Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not represent harmful or dangerous conditions.

21