Installation Instructions

Combustion Air and Ventilation for Appliances Located in Unconfined Spaces

Unconfined Space is a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour of the aggregate input rating of all appliances installed in that space, Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space

In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in Combustion Air and Ventilation for Appliances Located in Confined Spaces, b.

Combustion Air and Ventilation

for Appliances Located in Confined Spaces

Confined Space is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour of the aggregate input rating of all appliances installed in that space.

a. ALL AIR FROM INSIDE BUILDINGS:

(See Page 9 Figure 1, and Figure 2 below)

The confined space shall be provided with two permanent

openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all

spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the com- bined space shall be considered in making this determination.

Each opening shall have a minimum free area of one square inch per 1,000 BTU per hour of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches. One opening shall commence within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure.

(cont'd)

1.When directly communicating with the outdoors, each open- ing shall have a minimum free area of I square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure. (See Figure 3.)

2.When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure. (See Figure 4.)

I Figure 4 I

3.When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 BTU per hour of total input rating of all equipment in the enclosure. (See Figure5.)

ve_cr

Figure 2 ]

b. ALL AIR FROM OUTDOORS: (seeFigures 3-5)

The confined space shall be provided with two permanent openings, one commencing within I2 inches of the top and one commencing within 12 inches from the bottom of the enclosure. The openings shall communicate directly, or by

ducts, with the outdoors or spaces (crawl or attic) that freely. communicate with the outdoors.

Figure 3 ]

Figure 5 ]

4.When ducts are _ed, they shall be of the same cross-sectionalarea as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts shall not be less than 3 inches. (See Figure 5.)

5.Louvers and Grilles: In calculating free area, consideration shall be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used shall not be smaller than ¼ inch mesh. If the free area through a design of louver or grille is known, it should be used in calculating the size opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers will be 20-25 percent free area and metal louvers and grilles will have 60-75percent free area. Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.

6.Special Conditions Created by Mechanical Exhausting or Fireplaces: Opefiition of exhaust fans, ventilation systems, clothes dryers or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of installed gas utilization eqfiipment.

10

Page 10
Image 10
Kenmore 153.332462, 153.332362, 153.332418, 153.332318, 153.332562 owner manual Contd, ALL AIR from Inside Buildings

153.332562, 153.332362, 153.332418, 153.332462, 153.332318 specifications

The Kenmore series of air conditioners, specifically models 153.332318, 153.332562, 153.332418, 153.332462, and 153.332362, stands out in the crowded market of home cooling solutions. Each model offers unique features and technologies designed to enhance user experience and comfort in varying environments.

One of the main features across these models is their impressive cooling capacity. Engineered for spaces ranging from small apartments to larger rooms, these units utilize advanced cooling technologies to ensure efficient heat exchange and optimal cooling performance. With SEER ratings often above 15, they not only provide powerful cooling but also contribute to energy savings, reducing electricity bills, and environmental impact.

In addition to cooling efficacy, Kenmore air conditioners prioritize user convenience. Most models in this series are equipped with programmable thermostats, allowing users to set schedules according to their daily routines. This feature ensures that the room maintains a comfortable temperature when needed while conserving energy during off-hours. Some models also support remote control operation via mobile apps, giving users the flexibility to adjust settings from anywhere in the home.

Noise levels are a critical consideration in air conditioning units, and the Kenmore series excels in this aspect. With advanced sound dampening technology, these air conditioners operate quietly, making them ideal for bedrooms, home offices, or other noise-sensitive environments. Users can enjoy a cool atmosphere without the disruption of loud machinery.

Maintenance is also simplified with features like washable and reusable air filters. These filters help to improve indoor air quality by capturing dust, allergens, and other particulates. Regular cleaning ensures that the unit functions efficiently and prolongs its lifespan.

Furthermore, the sleek design of Kenmore air conditioners allows them to blend seamlessly with modern home decor, offering both aesthetic appeal and functional cooling power. With various models catering to different room sizes and cooling needs, the Kenmore 153.332318, 153.332562, 153.332418, 153.332462, and 153.332362 range provides versatile options for consumers looking for reliable and efficient air conditioning solutions. Overall, these units demonstrate Kenmore's commitment to quality and innovation in the HVAC market.