Installation Instructions (cont'd)

Venting (cont'd)

All vent gases must be completely vented to the outdoors of the structure (dwelling). Installonly the draft hood provided with the new water heater and no other draft hood.

Vent pipes must be secured at each joint with sheet metal screws.

TO

CHIMNEY

Gas Piping

AWARNING

Make sure the gas supplied is the same type listed on the model rating plate. The inlet gas pressure must not exceed J 14 inches water column Vzpound per square inch (3.5kPa). The minimum inlet gas pressure listed on the model rating [

p ate is for the purposeof input adjustment.

J

VENT PIPE INSTALLATION

There must be a minimum of 6" clearance between single wall vent pipe and any combustible material. Fill and seal any clear- ance between single wall vent pipe and combustible material with mortar mix, cement, or other noncombustible substance. For other than single wall, follow vent pipe manufacturer's clear- ance specifications. To insure a tight fit of the vent pipe in a brick chimney, seal around the vent pipe with mortar mix

cement,

Failure to have required clearancesbetween vent piping and

&WARNINGI

combustible material will result in a fire hazard.

Be sure vent pipe is properly connected to prevent escape of

AWARNINGI

!dangerousflue gaseswhich couldcausedeadlyasphyxiation.

AWARNING

Chemical vapor corrosion of the flue and vent system may occur if air for combustioncontainscertain chemicalvaper_ Spray can propellants,cleaning solvents,refrigerator and air conditioner refrigerants, swimming pool chemicals,calcium and sodium chloride,waxes, bleach,and processchemicalsare typicalcompoundswhichare potentiallycorrosive.

AWARNINGI

'the gascontrol valve is subjectedto pressuresexceeding ½ ] pound per square inch (3.SkPa), the damage to the gascon- I

trol valve couldresult in a fire or explosionfT_n leakingge_ I

&WARNING]

If the maingasline shuix_servingall gasappliancesk used, alsoturn "OFF" the gasat eachapplianceLeave.all gasappli- ancesshut oR'untilthewaterheaterinstallationiscomplete,

A gas line of sufficient size must be run to the water heater. Consult the latest edition of National Fuel Gas Code ANSI

Z223.1, also referred to as NFPA54 and the gas company concern- ing pipe size.

There must be:

A readily accessible manual shut off valve in the gas supply line serving the water heater, and

A drip leg (sediment trap) ahead of the gas control valve to help

prevent dirt and foreign materials from entering the gas control

V'dlve.

A flexible gas connector or a ground joint union between the shutoffvalve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the water heater. Use a soapy water solution, not a match or open flame. Rinse offsoapy solution and wipe dr_

Standard Modds are for _stallation up to 3,300 feet above sea level.

High Altitude Models are for installationfrom 3,300 to 5,500 feetabovesea level.

If a standard model is installedabove3,300 feet or a high altitude mode1 is installed above 5,500 feet, the input rating must be reduced at the rate of 4 percent for each 1,000 feetabove sea level.

Contact your local SearsService Center or gas utility for further information.

The applianceand its gasconnectionmust be leaktested

AWARNINGI

beforepacingtheapplance noperation.

14

Page 14
Image 14
Kenmore 153.332562 Venting contd, Gas Piping, Ate is for the purposeof input adjustment, Vent Pipe Installation

153.332562, 153.332362, 153.332418, 153.332462, 153.332318 specifications

The Kenmore series of air conditioners, specifically models 153.332318, 153.332562, 153.332418, 153.332462, and 153.332362, stands out in the crowded market of home cooling solutions. Each model offers unique features and technologies designed to enhance user experience and comfort in varying environments.

One of the main features across these models is their impressive cooling capacity. Engineered for spaces ranging from small apartments to larger rooms, these units utilize advanced cooling technologies to ensure efficient heat exchange and optimal cooling performance. With SEER ratings often above 15, they not only provide powerful cooling but also contribute to energy savings, reducing electricity bills, and environmental impact.

In addition to cooling efficacy, Kenmore air conditioners prioritize user convenience. Most models in this series are equipped with programmable thermostats, allowing users to set schedules according to their daily routines. This feature ensures that the room maintains a comfortable temperature when needed while conserving energy during off-hours. Some models also support remote control operation via mobile apps, giving users the flexibility to adjust settings from anywhere in the home.

Noise levels are a critical consideration in air conditioning units, and the Kenmore series excels in this aspect. With advanced sound dampening technology, these air conditioners operate quietly, making them ideal for bedrooms, home offices, or other noise-sensitive environments. Users can enjoy a cool atmosphere without the disruption of loud machinery.

Maintenance is also simplified with features like washable and reusable air filters. These filters help to improve indoor air quality by capturing dust, allergens, and other particulates. Regular cleaning ensures that the unit functions efficiently and prolongs its lifespan.

Furthermore, the sleek design of Kenmore air conditioners allows them to blend seamlessly with modern home decor, offering both aesthetic appeal and functional cooling power. With various models catering to different room sizes and cooling needs, the Kenmore 153.332318, 153.332562, 153.332418, 153.332462, and 153.332362 range provides versatile options for consumers looking for reliable and efficient air conditioning solutions. Overall, these units demonstrate Kenmore's commitment to quality and innovation in the HVAC market.