Service Tech Information

MANUAL ADVANCE REGENERATION CHECK

This check verifies proper operation of the valve motor, brine tank fill, brine draw, regeneration flow rates, and other controller functions. Always make the initial checks, and the manual initiated diagnostics.

NOTE: The faceplate display must show a steady time (not flashing). If an error code shows, first press the SELECT button to enter the diagnostic display.

1.Press the REGENERATION button and hold in for 3 seconds. *RECHARGE and Fill begin to flash (or clean backwash begins, if set) as the softener enters the fill cycle of regeneration.

*NOTE: If the CLEAN feature is set to ON, a clean- ing backwash (CLEAN and Bkwsh or Rinse flashes in the display, along with the minutes of the clean cycle remaining), precedes the recharge.

2.When FILL is on steady, remove the brinewell cover and, using a flashlight, observe fill water entering the tank.

3.If water does not enter the tank, look for an obstruct- ed nozzle, venturi, fill flow plug, brine tubing, or brine valve riser pipe.

CYCLE FLOW RATES (GALLONS PER MIN.)

FILL (flow to salt storage tank)

0.3 (1.1 liters)

BRINING (flow to drain)

.22 (.83 liters)

BRINE RINSE (flow to drain)

.15 (.57 liters)

MAX. BACKWASH (flow to drain)

2.0 (7.6 liters)

MAX. FAST RINSE (flow to drain)

2.0 (7.6 liters)

4.After observing fill, press the REGENERATION but- ton to move the softener into brining. A slow flow of water to the drain will begin. Verify brine draw from the brine tank by shining a flashlight into the brinewell and observing a noticeable drop in the liquid level.

NOTE: Be sure a salt bridge is not preventing water with salt contact.

5.If the softener does not draw brine:

nozzle and/or venturi dirty or defective.

nozzle and venturi not seated properly on gasket

restricted drain (check drain fitting and hose)

defective nozzle and venturi seal

other inner valve defect (rotor seal, rotor & disc, wave washer, etc.)

NOTE: If water system pressure is low, an elevated drain hose may cause back pressure, stopping brine draw.

Brine Valve

Float Setting

Float Stop

Float

10”

FIG. 57

6.Again press REGENERATION to move the softener into backwash. Look for a fast flow of water from the drain hose.

7.An obstructed flow indicates a plugged top distributor, backwash flow plu or drain hose.

8.Press RECHARGE to move the softener into fast rinse. Again look for a fast drain flow. Allow the sof- tener to rinse for a few minutes to flush out any brine that may remain in the resin tank from the brining cycle test.

9.To return the softener to service, press REGENERA- TION once more.

Questions? Call The Kenmore Water Line 1-800-426-9345

38

Page 38
Image 38
Kenmore 350 Series warranty Manual Advance Regeneration Check, Cycle Flow Rates Gallons PER MIN, Brine Valve Float Setting