Sizing Instructions
Many complaints about room air conditioners result from units that are
The following table contains guidelines for properly sizing a room air conditioner for a given area.
To size unit:
1.Determine size (in square feet) of area to be cooled; locate square footage in far left column of table below.
| Required Air Conditioner | |
Size of Area |
|
|
to be Cooled | attic; insulated | |
| Room below |
|
(in square feet) | ceiling above |
|
100 | 3500 to 4000 | |
150 | 4000 to 5000 | |
200 | 4500 to 5500 | |
250 | 5000 to 6000 | |
300 | 6000 to 7000 | |
35O | 6500 | to 7500 |
4OO | 7000 | to 8000 |
450 | 7500 to 8500 | |
5OO | 8000 to 9000 | |
60O | 9500 to 10500 | |
700 | 10500 | to 11500 |
800 | 11500 | to 13000 |
9OO | 12500 | to 14000 |
1000 | 13500 | to 15000 |
1200 | 16000 | to 17500 |
1400 | 18000 | to 20000 |
1600 | 20000 | to 22000 |
1800 | 22000 | to 24000 |
2000 | 24000 | to 26000 |
2.Choose
•Room below attic; insulated ceiling above.
•Room with occupied room above.
•Top floor under insulated roof.
3, Follow down
NOTE: When determining size of unit, also consider conditions at bottom of table. For best results, choose air conditioner with cooling capacity (Btus per hour) closest to, but not exceeding, estimated size.
Cooling |
|
| ||
|
|
| Top floor under | |
occupied |
|
| insulated | roof |
Room with |
|
| (no attic) |
|
room above |
|
|
| |
4000 to 4500 | 4500 to 5000 | |||
4500 | to 5000 | 5500 to 6500 | ||
5000 | to 6000 | 6000 to 7000 | ||
5500 | to 6500 | 7500 to 8500 | ||
6500 | to 7500 | 8500 to 9500 | ||
7000 | to 8000 | 10000 | to 11000 | |
8000 | to 9000 | 11000 | to 12000 | |
8500 | to 9500 | 11500 | to 12500 | |
9500 | to 10500 | 13000 | to 14000 | |
11000 | to 12000 | t 5000 to 16000 | ||
12000 | to 13000 | 17000 | to 18000 | |
13500 | to 14500 | 19000 | to 20000 | |
14500 | to 16000 | 21000 | to 22000 | |
15500 |
| to 17000 | 23000 | to 24500 |
18000 |
| to 20000 | 26500 | to 28500 |
21 000 to 230O0 | 30500 | tO 32500 | ||
23000 to 25000 |
|
| ||
25500 |
| to 27500 |
|
|
28000 |
| to 30000 |
|
|
Additional conditions:
•If normal occupancy of area is more than two people, add 600 Btu/hour per person. If normal occupancy is one person, subtract 600 Btu/hour.
•Add 1200 Btu/hour if area includes a kitchen,
•If room is heavily shaded, subtract 10 percent from total capacity. Increase by 10 percent if area is very sunny.