Kenmore 70129, 78189, 70089, 78079 owner manual Sizing Instructions

Models: 78079 70089 78189 70129

1 28
Download 28 pages 63.92 Kb
Page 5
Image 5
Sizing Instructions

Sizing Instructions

Many complaints about room air conditioners result from units that are over-sized or under-sizedfor a given area. Over-sized units cool an area before humidity can be adequately removed, so air feels cold and clammy. Under-sized units do not sufficiently cool an area.

The following table contains guidelines for properly sizing a room air conditioner for a given area.

To size unit:

1.Determine size (in square feet) of area to be cooled; locate square footage in far left column of table below.

 

Required Air Conditioner

Size of Area

 

 

to be Cooled

attic; insulated

 

Room below

 

(in square feet)

ceiling above

 

100

3500 to 4000

150

4000 to 5000

200

4500 to 5500

250

5000 to 6000

300

6000 to 7000

35O

6500

to 7500

4OO

7000

to 8000

450

7500 to 8500

5OO

8000 to 9000

60O

9500 to 10500

700

10500

to 11500

800

11500

to 13000

9OO

12500

to 14000

1000

13500

to 15000

1200

16000

to 17500

1400

18000

to 20000

1600

20000

to 22000

1800

22000

to 24000

2000

24000

to 26000

2.Choose right-hand column showing location of room in building:

Room below attic; insulated ceiling above.

Room with occupied room above.

Top floor under insulated roof.

3, Follow down right-hand column, reading horizontally from square footage to lind approximate air conditioner capacity (in Btus per hour) required to adequately cool designated area.

NOTE: When determining size of unit, also consider conditions at bottom of table. For best results, choose air conditioner with cooling capacity (Btus per hour) closest to, but not exceeding, estimated size.

Cooling Capacity--Btu/hour

 

 

 

 

 

Top floor under

occupied

 

 

insulated

roof

Room with

 

 

(no attic)

 

room above

 

 

 

4000 to 4500

4500 to 5000

4500

to 5000

5500 to 6500

5000

to 6000

6000 to 7000

5500

to 6500

7500 to 8500

6500

to 7500

8500 to 9500

7000

to 8000

10000

to 11000

8000

to 9000

11000

to 12000

8500

to 9500

11500

to 12500

9500

to 10500

13000

to 14000

11000

to 12000

t 5000 to 16000

12000

to 13000

17000

to 18000

13500

to 14500

19000

to 20000

14500

to 16000

21000

to 22000

15500

 

to 17000

23000

to 24500

18000

 

to 20000

26500

to 28500

21 000 to 230O0

30500

tO 32500

23000 to 25000

 

 

25500

 

to 27500

 

 

28000

 

to 30000

 

 

Additional conditions:

If normal occupancy of area is more than two people, add 600 Btu/hour per person. If normal occupancy is one person, subtract 600 Btu/hour.

Add 1200 Btu/hour if area includes a kitchen,

If room is heavily shaded, subtract 10 percent from total capacity. Increase by 10 percent if area is very sunny.

Page 5
Image 5
Kenmore 70129, 78189, 70089, 78079 owner manual Sizing Instructions